Table 15. Maximum FC cable lengths (continued)
Data rate
OM1 maximum length
OM2 maximum length
OM3 maximum length
16 Gbps
15m
35m
100m
Connecting disk shelf power cables
Prerequisites
Each disk shelf has two power supplies. Connect each power supply to redundant AC power sources, so the loss of one power
supply does not cause the shelf to power off.
About this task
FS25 shelves have one power cord per power supply for a total of two power cords. DS60 shelves have two power cords per
power supply for a total of four power cords.
Steps
1. Plug the power cords into both power supplies on the disk shelf.
2. If the disk shelf has a retention bail, secure the power cord with the retention bail. The bail prevents the power cord from
pulling out of the connector.
3. For DS60 shelves, connect each power supply to redundant power sources in the rack.
4. Repeat the preceding steps for each shelf in the rack.
Connecting controller power cables and powering on
Prerequisites
Connect the power cables to power on the disk shelves before powering on the controller.
Steps
1. Verify the jumpers at the bottom of each PDU are set correctly. From the back of the rack, Zone B is on the left-hand and
Zone A is on the right-hand side. The following images show the jumpers for each type of power connection
●
Single phase power
Figure 69. Single phase power
●
Three phase delta power
Connect Cables and Power On
61
Summary of Contents for PowerProtect DD9400
Page 1: ...Dell EMC PowerProtect DD9400 System Installation Guide September 2020 Rev 03...
Page 57: ...Figure 65 Single node DD9400 with DS60 shelves Connect Cables and Power On 57...
Page 58: ...Figure 66 HA DD9400 with DS60 shelves 58 Connect Cables and Power On...
Page 63: ...Figure 72 Routing cables through the CMA brackets Connect Cables and Power On 63...