3. Open the main gas supply.
4. Check the gas supply pressure at the pressure outlet
C
on the gas
valve unit.
WARNING
¼
To ascertain the gas types permitted, see chapter:
5. Check the tightness of the gas connections made after the gas
valve unit in the boiler.
6. Check the tightness of the gas line, including the gas valves. The
test pressure must not exceed 60 mbar.
7. Purge the gas supply pipe within the boiler by unscrewing the
pressure outlet on the gas block. Tighten the measurement point
when the pipe has been sufficiently purged.
8. Check the tightness of the gas connections in the boiler.
5.2.3.
Hydraulic circuit
4
Check the condensate discharge siphon; it must be filled with
clean water up to the mark.
4
Check that there are no leaks on the hydraulic connections.
5.2.4.
Electrical connections
4
Check the electrical connections.
5.3
Putting the appliance into operation
1. Open the main gas supply.
2. Turn on the boiler using the on/off switch.
T001518-B
C
8
22
24
20
l
0
C003159-A
AGC 10/15 - AGC 15 - AGC 25 - AGC 35
5. Commissioning
20/01/2012 - 300026081-001-B
69