A
Do not connect anything to the terminal block.
Z
Connect the heating pump (Circuit
A
).
E
D.H.W. load pump
R
Hot water storage tank sensor
T
Buffer tank.
Y
outside temperature sensor
U
Connect the DHW tank anode.
If the tank is not fitted with an impressed current
anode, put the simulation connector in place
(delivered with the DHW sensor - package
AD212).
I
Solar sensor probe.
O
Connect the solar station to the solar collectors.
P
Domestic hot water boiler.
Connect the DHW sensor.
a
DHW sensor
z
Do not connect anything to the terminal block.
Settings to be made for this type of installation
Parameters
Access
Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM
menu
EXTENDED
¼
"Displaying the parameters in extended mode", page
I.SYST
(1)
Installer level
#SYSTEM
menu
ST.TANK+DHW
¼
"Setting the parameters specific to the installation",
P.DHW:
(1)
Installer level
#SYSTEM
menu
PUMP
BOILER PUMP
Installer level
#SYSTEM
menu
ALL
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
The DHW tank is loaded from the storage tank. If, during
DHW loading, the temperature of the storage tank falls
below the primary DHW set point (parameter
PRIM.TEMP.DHW), the boiler maintains the latter at
temperature to guarantee the loading of the DHW tank
The heating zone is maintained at the set temperature
calculated according to the outside temperature. The zone
is reheated when the heating buffer temperature sensor
falls -6°C below the calculated set temperature. Reheating
in the heating zone stops when the heating buffer
temperature rises above the calculated set temperature.
AGC 10/15 - AGC 15 - AGC 25 - AGC 35
4. Installation
20/01/2012 - 300026081-001-B