E
Connect the DHW sensor (Package AD212).
R
Connect the outside temperature sensor.
T
Connect the DHW tank anode.
CAUTION
4
If the tank is fitted with a Titan Active
System® impressed current anode,
connect the anode to the inlet (+ on the
anode, - on the tank).
4
If the tank is not fitted with an impressed
current anode, put the simulation
connector in place (delivered with the DHW
sensor - package AD212).
Y
Connect a safety thermostat if the heating circuit is for
underfloor heating.
4
Remove the bridge.
4
Connect the wires from the safety thermostat to the
connector.
U
CAUTION
Do not connect anything to the
Mr
outlet on the
terminal block. The reversal valve is connected
to the PCU PCB in the boiler.
I
Do not connect anything to the terminal block.
Settings to be made for this type of installation
Parameters
Access
Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM
menu
EXTENDED
¼
If a domestic hot water looping pump
is connected to
M
A
on the terminal
block:
O.PUMP A
(1)
Installer level
#SYSTEM
menu
DHW LOOP
¼
specific to the installation", page
If safety thermostat is connected to
BL
on the connection terminal block:
IN.BL
Installer level
#PRIMARY INSTAL.P
menu
TOTAL STOP
¼
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
AGC 10/15 - AGC 15 - AGC 25 - AGC 35
4. Installation
20/01/2012 - 300026081-001-B
45