D-500 MK3 User Manual Firmware V-7.5
- 172 -
This protection function measures the frequency of the mains for each period. If the frequency is outside
limits for 4 successive periods, it detects a mains failure. The response time of the mains frequency is
approximately 4 cycles.
Related parameters:
Mains Frequency Low Limit
Mains Frequency High Limit
The mains phase voltages are measured twice a second and compared with predefined high and low
limits. If at least one of the phase voltages is outside limits, this will mean a mains failure. The response
time is approximately 500ms.
Related parameters:
Mains Voltage Low Limit
Mains Voltage High Limit
The mains active power is measured for each period. If the genset system supplies power to mains and
this power exceeds the predefined limit, this will mean a mains failure.
The mains reverse power detector has a variable response time. For a power not exceeding 2 times the
predefined limit the response time is 8 cycles. The response time is reduced with larger reverse powers. It
is approximately 1 cycle with a reverse power of 8 times the predefined limit.
Related parameter:
Mains Reverse Power Limit
If the parameter is set to zero, then the protection function will be disabled.
The unit counts the time after the last detection of the mains frequency pulses. If no mains pulses is
detected for a period corresponding to 2,5 times the
Mains Frequency Low Limit
, a mains failure alarm
is generated.
Related parameter:
Mains Frequency Low Limit
If the parameter is set to zero, then the protection function will be disabled.
32.6. NO FREQUENCY FUNCTION
32.5. MAINS REVERSE POWER FUNCTION
32.4. OVER/UNDER VOLTAGE FUNCTION
32.3. OVER/UNDER FREQUENCY FUNCTION
Summary of Contents for D-500 MK3
Page 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...