D-500 MK3 User Manual Firmware V-7.5
- 168 -
The
Export to Mains
mode allows the multi genset system to supply the mains power grid under
constant power factor. Thus the multi genset system will be part of the mains power supply system.
The Export to Mains mode is activated by setting the program parameter
Power Export Enable
. This
operating mode is not compatible with Peak Lopping. Thus
Peak Lopping Enable
parameter must be 0.
When
Export to Mains
is enabled, the mains voltages and frequency are within limits and the D700 in
AUTO
mode, the unit will run the genset system, synchronize with mains and close the Load Contactor.
Then the output active power of the genset system will ramp-up at the rate defined in program parameter
Active Power Ramp
. The reactive power is continuously adjusted in order to hold the power factor
constant (defined in
Exported Power Factor
).
When the requested output power is reached, the ramping will be terminated. The requested power is
defined by
Exported Power
program parameter.
The G59 protections for mains failure in parallel are active during the Export to Mains operation, with the
exception of
Mains Reverse Power
protection. If a mains failure is detected during paralleling, then the
mains contactor will open, and the D700 will continue to feed the local load. When the mains is restored,
then the genset system will resume
Export to Mains
operation.
The Export to Mains operation is compatible with the
Weekly Operating Schedule
. Thus the genset can
be programmed for supplying the mains only during given time intervals.
The power export mode may be disabled momentarily with an external signal. In order to achieve this, a
digital input should be programmed as
Disable Power Export
function input. More information about
input programming is found in the
PROGRAMMING
chapter.
31.2. POWER EXPORT TO MAINS
GENSET
LOAD
MAINS
Summary of Contents for D-500 MK3
Page 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...