D-500 MK3 User Manual Firmware V-7.5
- 104 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Genset Current
Transformer Primary
Amp
1
5000
500
This is the rated value of current
transformers at the genset CT inputs.
All transformers must have the same
rating. The secondary of the
transformer will be 5 Amps.
Mains Current
Transformer Primary
Amp
1
5000
500
This is the rated value of current
transformers at the mains CT inputs.
All transformers must have the same
rating. The secondary of the
transformer will be 5 Amps.
Voltage Transformer
Ratio
-
0
5000
1.0
This is the voltage transformer ratio.
This value will multiply all voltage and
power readings. If transformers are not
used, the ratio should be set to 1.0
Nominal Voltage
V-AC
0
300
230
The nominal value of genset and mains
voltages. Voltage limits are defined by
reference to this value.
Nominal Frequency
Hz
0
500
50
The nominal value of genset and mains
frequency. Frequency limits are defined
by reference to this value.
Nominal Voltage-2
V-AC
0
300
120
When secondary voltage is selected,
this is the nominal value of genset and
mains voltages. Voltage limits are
defined by reference to this value.
Nominal Frequency-2
Hz
0
500
60
When secondary frequency is selected,
this is nominal value of genset and
mains frequency. Frequency limits are
defined by reference to this value.
Nominal Voltage-3
V-AC
0
300
120
When tertiary voltage is selected, this is
the nominal value of genset and mains
voltages. Voltage limits are defined by
reference to this value.
Nominal Frequency-3
Hz
0
500
60
When tertiary frequency is selected, this
is nominal value of genset and mains
frequency. Frequency limits are defined
by reference to this value.
Mains Voltage Low Limit
%
V-100 V+100
V-20%
If one of the mains phases goes under
this limit, it means that the mains are off
and starts the transfer to the genset in
AUTO
mode. The value is defined with
reference to Nominal Voltage.
Mains Voltage High Limit
%
V-100 V+100 V+20%
If one of the mains phases goes over
this limit, it means that the mains are off
and starts the transfer to the genset in
AUTO
mode. The value is defined with
reference to Nominal Voltage.
Mains Voltage Fail Timer
sec
0
10
1
If at least one of the mains phase
voltages goes outside of the limits
during this timer, it means that the
mains are off and it starts the transfer to
the genset in
AUTO
mode.
17.2. ELECTRICAL PARAMETERS GROUP
Summary of Contents for D-500 MK3
Page 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...