D-500 MK3 User Manual Firmware V-7.5
- 62 -
Term Function
Technical data
Description
19
SENDER GROUND
Input
Ground potential for analog senders.
Connect to the engine body, close to
senders.
Connect to the oil pressure sender.
Do not connect the sender to other
devices.
20
ANALOG SENDER 1
(OIL PRESSURE SENDER)
Resistor measuring
input,
0-5000 ohms
Connect to the oil pressure sender.
Do not connect the sender to other
devices.
21
ANALOG SENDER 2
(COOLANT TEMP. SENDER)
Connect to the coolant temperature
sender. Do not connect the sender to
other devices.
22
ANALOG SENDER 3
(FUEL LEVEL SENDER)
Connect to the fuel level sender.
Do not connect the sender to other
devices.
23
ANALOG SENDER 4
(OIL TEMP SENDER)
Connect to the oil temperature sender.
Do not connect the sender to other
devices.
24
SENDER 5V
Output
This terminal provides +5V supply for
active type senders. The maximum output
current is 50mA. An internal electronic
fuse protects the supply against overloads
or short circuits.
25
MPU +
Analog input, 0.5 to
30V-AC
Connect the MPU unit to these inputs
Use a twisted cable pair or coaxial cable
for best results.
26
GND
27
CANBUS-H
Digital communication
port
Connect the J1939 port of an electronic
engine to these terminals.
The 120 ohm terminating resistors are
inside the unit. Please do not connect
external resistors.
Use a twisted cable pair or coaxial cable
for best results.
28
CANBUS-L
Term Function
Technical data
Description
51
GENERATOR CONTACTOR
Relay output, 16A-AC This output provides energy to the
generator contactor. If the generator
phases do not have acceptable voltage or
frequency values, the generator contactor
will be de-energized. In order to provide
extra security, the normally closed contact
of the mains contactor should be serially
connected to this output.
52
GEN-L1
Generator phase
inputs, 0-300V-AC
Connect the generator phases to these
inputs. The generator phase voltages
upper and lower limits are programmable.
54
GEN-L2
56
GEN-L3
58
GENERATOR NEUTRAL
Input, 0-300V-AC
Neutral terminal for the generator phases.
Summary of Contents for D-500 MK3
Page 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...