D-500 MK3 User Manual Firmware V-7.5
- 108 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Genset Overload Limit
kW
0
50000
0
If the total genset active power goes over
this limit when feeding the load, this will
generate a genset overload loaddump
alarm. If this parameter is set to 0 then
overload fault is not monitored.
Genset Overload Fail
Timer
sec
0
120
3
If the genset active power is over the
limit during this timer, an overload fault
will occur.
Load Shedding Low Limit
kW
0
50000
0
If the genset power goes below this limit
then the load shedding relay will be
deactivated. Review chapter “Load
Shedding” for more details.
Load Shedding High
Limit
kW
0
50000
0
If the genset power goes above this
limit then the load shedding relay will be
activated. Review chapter “Load
Shedding” for more details.
Load Add Delay
sec
0
240
0
This is the minimum delay between 2
load_add pulses.
Review chapter “Load
Shedding” for more details.
Load Subtract-Add Delay
min
0
120
0
This is the minimum delay required for a
load_add pulse after a load_substract
pulse. Review c
hapter “Load Shedding”
for more details.
Mains Waiting Timer
sec
0
50000
30
This is the time between the mains
voltages and frequency entered within
the limits and the generator contactor is
deactivated.
Mains Connection
Topology
-
0
7
5
This is the connection topology of mains
voltages and CTs. Detailed
explanations are given in the chapter:
“TOPOLOGIES”.
0:
2 phase, 3 wire L1-L2
1:
2 phase, 3 wire L1-L3
2:
3 phase, 3 wire
3:
3 phase, 3 wire, 2CTs L1-L2
4:
3 phase, 3 wire, 2CTs L1-L3
5:
3 phase, 4 wire star
6:
3 phase, 4 wire delta
7:
single phase, 2 wire
Genset Connection
Topology
-
0
7
5
This is the connection topology of
genset voltages and CTs. Detailed
explanations are given in the chapter:
TOPOLOGIES.
0:
2 phase, 3 wire L1-L2
1:
2 phase, 3 wire L1-L3
2:
3 phase, 3 wire
3:
3 phase, 3 wire, 2CTs L1-L2
4:
3 phase, 3 wire, 2CTs L1-L3
5:
3 phase, 4 wire star
6:
3 phase, 4 wire delta
7:
single phase, 2 wire
17.2. ELECTRICAL PARAMETERS GROUP (continued)
Summary of Contents for D-500 MK3
Page 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...