D-500 MK3 User Manual Firmware V-7.5
- 99 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Modem / GPS Selection
-
0
5
0
0:
no MODEM / no GPS
1:
Internal MODEM, no GPS
2:
External MODEM, no GPS
3:
External generic MODEM, no GPS
4:
no MODEM, RS-232 GPS
5:
Internal MODEM, RS-232 GPS
External Modem / GPS
Baud Rate
bps
2400 115200 115200
This is the data rate of the RS-232 port
for the external modem / GPS.
GSM Sim Card Pin
-
0
9999
0
If the GSM SIM card uses pin number,
enter the pin number here. If incorrect
pin number is entered, then the SIM
card will not operate.
SMS Enable
-
0
1
0
0:
SMS messages disabled
1:
SMS messages enabled
GPRS Connection
Enable
-
0
1
0
0:
GPRS disabled
1:
GPRS enabled
Web Programming
Enable
-
0
1
0
0:
Web programming disabled
1:
Web programming enabled
Web Control Enable
-
0
1
0
0:
Web control disabled
1:
Web control enabled
Web Refresh Rate
sec
0
240
10
The unit will refresh the web page with
this interval.
Ping Period
sec
30
900
120
The unit will check the availability of the
internet connection with this interval.
Rainbow Scada Refresh
Rate
sec
0
65535
60
The unit will update the distant
monitoring terminal with this rate.
Rainbow Scada
Address-1 Port
-
0
65535
90
This is the port number of the first
monitoring terminal address.
Rainbow Scada
Address-2 Port
-
0
65535
90
This is the port number of the second
monitoring terminal address.
Web Server Port
-
0
65535
80
This is the port number of the internal
web server. The unit will answer queries
to this port only.
Modbus TCP/IP Port
-
0
65535
502
Internal Modbus TCP/IP server’s port
number. The unit answers Modbus
requests to this port only.
SMTP Port
-
0
65535
587
This is the port number used for e-mail
sending.
Ethernet to RS-485
Modbus Gateway Enable
-
0
1
0
0:
ethernet-modbus gateway function
disabled.
1:
ethernet-modbus gateway function
enabled. The unit will redirect Modbus
requests from ethernet to the RS-485
port.
GPRS to RS-485
Modbus Gateway Enable
-
0
1
0
0:
gprs-modbus gateway function
disabled.
1:
gprs-modbus gateway function
enabled. The unit will redirect Modbus
requests from GPRS to the RS-485
port.
RS-485 Enable
-
0
1
1
0:
RS-485 port disabled
1:
RS-485 port enabled
Modbus Address
-
0
240
1
This is the modbus controller identity
used in Modbus communication.
17.1. CONTROLLER CONFIGURATION GROUP (continued)
Summary of Contents for D-500 MK3
Page 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...