Parameter Definition
Unit
Min
Max
Factory
Set
Description
System Reserve Power
kW
0
65000
20
The master keeps this amount of extra
power available during whole operation
under load as a safety against a sudden
load surge.
Load Management
Method
-
0
1
0
0:
Equal Aging
1:
Smart
Dead Busbar Limit for
Multi Genset System
VAC
0
300
50
This parameter defines the minimum
voltage for the detection of a live busbar.
Governor Control Enable
-
0
1
1
0:
Governor control disabled.
1:
Governor control enabled.
Governor Output
Reverse Polarity
-
0
1
0
0:
Governor control normal polarity
(speed increases with voltage increase).
1:
Governor control reverse polarity
(speed decreases with voltage increase).
Governor Output Low
Lim
%
0
100.0
0.0
This parameter defines governor control
output low limit. Limits from 0V to 10V
can be set by this parameter
Governor Output Gain
Lim
%
0
100.0
100.0
This parameter defines governor control
output gain.
Governor Output Rest
Point
%
0
100.0
50.0
This is the rest value of the governor
control output at no load.
Governor Droop Enable
-
0
1
0
0:
Governor droop mode disabled.
1:
Governor droop mode enabled.
Governor Output Droop
%
0
100.0
0
The controller will inject this quantity of
droop at the genset rpm at 100% active
power load.
AVR Control Enable
-
0
1
1
0:
AVR control disabled.
1.
AVR control enabled.
AVR Reverse Polarity
-
0
1
1
0:
AVR control normal polarity (voltage
increases with value increase).
1:
AVR control reverse polarity (voltage
decreases with value increase).
AVR Output Low Limit
%
0
100.0
0.0
This parameter defines AVR output low
limit. Limits from -3.0V to +3.0V can be
set by this parameter
AVR Output High Limit
%
0
100.0
100.0
This parameter defines AVR output high
limit. Limits from -3.0V to +3.0V can be
set by this parameter
AVR Output Rest Point
%
0
100.0
50.0
This is the rest value of the AVR control
output at no load.
AVR Droop Enable
-
0
1
0
0:
AVR droop mode disabled.
1:
AVR droop mode enabled.
AVR Output Droop
%
0
100.0
0.0
The controller will inject this quantity of
droop at the genset voltage at 100%
reactive power load.
Excitation Loss Alarm
Level
-
0
3
2
0:
not used
1:
engine shutdown
2:
load-dump alarm
3:
warning
No Break Transfer
Enable
-
0
1
0
0:
only interrupted transfer enabled
1:
no break transfer enabled
Synchronization Fail
Timeout
sec
0
600
30
If the phase and voltage synchronization
is not successful before the expiration of
this timer, then a Synchronization Fail
warning is given and the transfer will be
performed with interruption.
Summary of Contents for D-500 MK3
Page 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...