D-500 MK3 User Manual Firmware V-7.5
- 109 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Mains Contactor Timer
sec
0
600
0.5
This is the period after the generator
contactor has been deactivated and
before the mains contactor has been
activated.
Mains MCB Close Pulse
sec
0
10
0.5
After the mains MCB_undervoltage coil
is energized and mains
MCB_undervoltage coil timer is
elapsed, the mains MCB_close relay
will be activated during this period.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
Mains MCB Open Pulse
sec
0
10
0.5
The mains MCB_open relay will be
activated during this period.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
Mains MCB
Undervoltage Coil Timer
sec
0
10
0.5
The mains MCB_undervoltage coil is
energized during this period before the
mains MCB_close relay is activated.
Review chapter
“
Motorized Circuit
Breaker Control
” for more details.
MCB Alarm Level
-
0
1
0
0:
shutdown alarm
1:
loaddump alarm
Mains MCB Fail Timer
sec
0
600
2.0
If a mains MCB feedback input is
defined and if the mains MCB fails to
change position before the expiration of
this timer, then a fault condition occurs.
Mains Phase Order
Check Enable
-
0
1
0
0:
mains phase order checking disabled
1:
if mains phase order is faulty, then a
warning is given and mains contactor
deenergized.
Genset Contactor Timer
sec
0
600
0.5
This is the period after the mains
contactor has been deactivated and
before the genset contactor has been
activated.
Genset MCB Close Pulse
sec
0
10
0.5
After the genset MCB_undervoltage coil
is energized and genset
MCB_undervoltage coil timer is
elapsed, the genset MCB_close relay
will be activated during this period.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
Genset MCB Open Pulse
sec
0
10
0.5
The genset MCB_open relay will be
activated during this period.
Review chapter
“
Motorized Circuit
Breaker Control
” for more details.
Genset MCB
Undervoltage Coil Timer
sec
0
10
0.5
The genset MCB_undervoltage coil is
energized during this period before the
genset MCB_close relay is activated.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
17.2. ELECTRICAL PARAMETERS GROUP (continued)
Summary of Contents for D-500 MK3
Page 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...