D-500 MK3 User Manual Firmware V-7.5
- 110 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
GCB Alarm Level
-
0
1
0
0:
shutdown alarm
1:
loaddump alarm
Genset MCB Fail Timer
sec
0
600
2.0
If a genset MCB feedback input is
defined and if the genset MCB fails to
change position before the expiration of
this timer, then a fault condition occurs.
Genset Phase Order
Check Enable
-
0
1
0
0:
genset phase order checking
disabled
1:
if genset phase order is faulty, then a
genset phase order fail loaddump alarm
is given.
Busbar Fail Timer
sec
0
30
2.0
When a genset closes to the Busbar, if
the mater genset controller does detect
the Busbar voltage at the expiration of
this period, a “BUSBAR FAIL” fault
condition will occur.
Busbar Ready Timer
sec
0
30
2.0
This is the delay after all generators
close to the busbar and before the
master genset controller acknowledges
“Busbar ready” signal.
Multi Load Subtract
Power Level
kW
0
65000
0
When the genset active power goes
over this limit, the controller will start
substracting load as described in
chapter
Five Step Load Management
.
Multi Load Add Power
Level
kW
0
65000
0
When the genset active power goes
below this limit, the controller will start
adding load as described in chapter
Five Step Load Management
.
Multi Load Substract
Start Delay
sec
0
36000
0
If the load stays over the
Multi Load
Substract Power Level
parameter
during this timer, then 1 step of load is
substracted.
Multi Load Substract
Wait Delay
sec
0
36000
0
This is the minimum period between
two load subtract operations.
Multi Load Add Start
Delay
sec
0
36000
0
If the load stays below the
Multi Load
Add Power Level
parameter during this
timer, then 1 step of load is added.
Multi Load Add Wait
Delay
sec
0
36000
0
This is the minimum period between
two load add operations.
Excess power Warning
Limit
kW
0
50000
0
If the genset active power goes above
this limit then the controller will give an
Excess Power Warning.
17.2. ELECTRICAL PARAMETERS GROUP (continued)
Summary of Contents for D-500 MK3
Page 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...