D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 10 -
Before installation:
▪
Read the user manual carefully, determine the correct connection diagram.
▪
Remove all connectors and mounting brackets from the unit, then pass the unit through the
mounting opening.
▪
Put mounting brackets and tighten. Do not tighten too much, this can brake the enclosure.
▪
Make electrical connections with plugs removed from sockets, then place plugs to their sockets.
▪
Be sure that adequate cooling is provided.
▪
Be sure that the temperature of the environment will not exceed the maximum operating
temperature in any case.
Below conditions may damage the device:
▪
Incorrect connections.
▪
Incorrect power supply voltage.
▪
Voltage at measuring terminals beyond specified range.
▪
Voltage applied to digital inputs over specified range.
▪
Current at measuring terminals beyond specified range.
▪
Overload or short circuit at relay outputs
▪
Connecting or removing data terminals when the unit is powered-up.
▪
High voltage applied to communication ports.
▪
Ground potential differences at non-isolated communication ports.
▪
Excessive vibration, direct installation on vibrating parts.
Below conditions may cause abnormal operation:
▪
Power supply voltage below minimum acceptable level.
▪
Power supply frequency out of specified limits
▪
Phase order of voltage inputs not correct.
▪
Current transformers not matching related phases.
▪
Current transformer polarity incorrect.
▪
Missing grounding.
Current Transformers must be used for current
measurement.
No direct connection allowed.
1. INSTALLATION INSTRUCTIONS
Summary of Contents for D-200 MK2
Page 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Page 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Page 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...