D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 87 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Coolant Cooler On
°C
0
250
90
If the coolant temp is above this limit then
the cooler relay function will become
active.
Coolant Cooler Off
°C
0
250
80
If the coolant temp is below this limit then
the cooler relay function will become
inactive.
Coolant Heater On
°C
0
250
50
If the coolant temp is below this limit then
the heater relay function will become
active.
Coolant Heater Off
°C
0
250
60
If the coolant temp is above this limit then
the heater relay function will become
inactive.
Fan Overrun Timer
sec
0
240
0
The cooler relay will stay active during
this timer after the coolant temp is below
“Coolant Cooler Off” limit.
Canopy Fan Turn-On
°C
0
250
90
If the canopy temp is above this limit then
the canopy fan relay function will become
active.
Canopy Fan Turn-Off
°C
0
250
80
If the canopy temp is below this limit then
the canopy fan relay function will become
inactive.
Ambient Fan Turn-On
°C
0
250
90
If the ambient temp is above this limit
then the ambient fan relay function will
become active.
Ambient Fan Turn-Off
°C
0
250
80
If the ambient temp is below this limit
then the ambient fan relay function will
become inactive.
Service-1 Engine Hours
hours
0
5000
250
The
SERVICE REQUEST
led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no
SERVICE REQUEST
will
be generated depending on service-1
engine hours.
Service-1 Period
month
0
24
6
The
SERVICE REQUEST
led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no
SERVICE REQUEST
will be
indicated depending on Service-1
Period.
Service-1 Alarm Level
-
0
3
3
0:
no action
1:
shutdown alarm
2:
loaddump alarm
3:
warning
16.3. ENGINE PARAMETERS GROUP (continued)
Summary of Contents for D-200 MK2
Page 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Page 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Page 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...