D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 23 -
Structure:
Relay output, normally closed contact. One terminal is internally
connected to mains phase L1 input.
Max switching current:
16A @250VAC
Max switching voltage:
440VAC
Max switching power:
3000VA
Structure:
Relay output, normally open contact. One terminal is internally
connected to genset phase L1 input.
Max switching current:
16A @250VAC
Max switching voltage:
440VAC
Max switching power:
4000VA
Structure:
Negative pulling protected semiconductor output. One terminal is
connected to battery negative.
Function
programmable, selectable from list.
Max continuous current:
1.0 ADC
Max switching voltage:
33 VDC
Overvoltage protection:
40 VDC
Short circuit protection:
> 1.7 ADC
Reverse voltage
protection:
500 VDC
3.9. GENERATOR CONTACTOR OUTPUT
3.10. DIGITAL OUTPUTS
3.8. MAINS CONTACTOR OUTPUT
Summary of Contents for D-200 MK2
Page 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Page 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Page 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...