D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 76 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Fuel Pulses from MPU
input
-
0
1
0
0:
MPU input is used for engine speed
detection
1:
MPU input is used for reading the
flowmeter pulses during fuel filling.
Fuel Pulses per Volume
-
0
65000
1000
This is the number of pulses produced
by the flowmeter for the unit volume.
This parameter is characteristic of the
flowmeter used and should be set
according to the flowmeter data.
Fuel Counter Unit
Lt/gal
-
-
liters
This is the unit for the fuel counter
SMS on Engine
Run/Stop
-
0
1
0
This parameter controls SMS sending
when the engine runs or stops. No
warnings generated.
0:
no SMS on engine run/stop
1:
SMS sent on engine run/stop
E-mail on Engine
Run/Stop
-
0
1
0
This parameter controls e-mail sending
when the engine runs or stops. No
warnings generated.
0: no e-mail on engine run/stop
1: e-mail sent on engine run/stop
Fuel Counter Type
-
0
1
0
This parameter determines the purpose
of fuel pulses
0: Fuel filling pulses, increment fuel
counter
1: Fuel consumption pulses, display
consumption.
Dual Genset Equal Aging
Enabled
-
0
1
0
0: Equal aging not enabled
1: Equal aging enabled
CT Secondary Rating
-
0
1
0
0: xxx/5A
1: xxx/1A
Maintenance Done
Warning Enable
-
0
1
0
If enabled, the unit will generate a non-
visual warning when maintenance
counters are reset. In consequence,
SMS and e-mails will be sent, the
warning will be visible on the central
monitoring system.
0: maintenance warning disabled
1: maintenance warning enabled
Stop Status Screens
-
0
1
0
0: Enable status screens
1: Disable status screens
Time Zone
min
-720
+720
0
This parameter adjusts the time zone of
the controller, in order to allow internal
real time clock to be synchronized to
the UTC time.
GSM Location
Information
-
0
1
0
0: no location information from GSM
1: location information read from GSM
system.
Disable STOP at
Loaddump
-
0
1
0
0: When Loaddump alarm occurs,
genset contactor opens and genset
runs until the end of the cooldown
period.
1: When Loaddump alarm occurs,
genset contactor opens but the genset
continues running without timeout.
16.1. CONTROLLER CONFIGURATION GROUP (continued)
Summary of Contents for D-200 MK2
Page 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Page 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Page 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...