D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 73 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Modem / GPS Selection
-
0
5
0
0:
no MODEM / no GPS
1:
Internal MODEM, no GPS
2:
External Datakom MODEM, no GPS
3:
External generic MODEM, no GPS
4:
no MODEM, RS-232 GPS
5:
Internal MODEM, RS-232 GPS
RS-232 Port
Baud Rate
bps
2400 115200 115200
This is the data rate of the RS-232 port
for the external modem / GPS.
GSM Sim Card Pin
-
0000
9999
0
If the GSM SIM card uses pin number,
enter the pin number here. If incorrect
pin number is entered, then the SIM card
will not operate.
SMS Enable
-
0
1
0
0:
SMS messages disabled
1:
SMS messages enabled
GPRS Connection
Enable
-
0
1
0
0:
GPRS disabled
1:
GPRS enabled
Rainbow Scada Refresh
Rate
sec
0
65535
5
The unit will update the distant
monitoring terminal with this rate.
Rainbow Scada
Address-1 Port
-
0
65535
0
This is the port number of the first
monitoring terminal address.
Rainbow Scada
Address-2 Port
-
0
65535
0
This is the port number of the second
monitoring terminal address.
RS-485 Enable
-
0
1
1
0:
RS-485 port disabled
1:
RS-485 port enabled
Modbus Address
-
0
240
1
This is the modbus controller identity
used in Modbus communication.
Oil Pressure Switch
Priority
-
0
1
0
0: crank cut is performed through oil
pressure switch and oil pressure sender
reading
1: crank cut is performed only through oil
pressure switch
Flashing Relay ON Timer
min
0
1200
0
Delayed Simulate Mains Operation:
max genset running time after Simulate
Mains signal disappears.
Dual Genset Systems: flashing relay ON
state duration timer.
Flashing Relay OFF
Timer
min
0
1200
0
Dual Genset Systems: flashing relay
OFF state duration.
Real Time Clock Adjust
-
0
255
117
This parameter trims precisely the real
time clock circuit. Values from 0 to 63
speed up the clock with 0.25sec/day
steps. Values from 127 to 64 slow down
the clock with 0.25sec/day steps.
Hysteresis Voltage
V-AC
0
30
8
This parameter provides the mains and
genset voltage limits with a hysteresis
feature in order to prevent faulty
decisions.
For example, when the mains are
present, the mains voltage low limit will
be used as the programmed low limit.
When the mains fail, the low limit will be
incremented by this value. It is advised
to set this value to 8 volts.
16.1. CONTROLLER CONFIGURATION GROUP (continued)
Summary of Contents for D-200 MK2
Page 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Page 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Page 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...