D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 81 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Genset Overload Limit
kW
0
50000
0
If the total genset active power goes over
this limit when feeding the load, this will
generate a genset overload loaddump
alarm. If this parameter is set to 0 then
overload fault is not monitored.
Genset Overload Fail
Timer
sec
0
120
3
If the genset active power is over the
limit during this timer, an overload fault
will occur.
Load Shedding Low Limit
kW
0
50000
0
If the genset power goes below this limit
then the load shedding relay will be
deactivated. Review chapter “Load
Shedding” for more details.
Load Shedding High
Limit
kW
0
50000
0
If the genset power goes above this
limit then the load shedding relay will be
activat
ed. Review chapter “Load
Shedding” for more details.
Load Add Delay
sec
0
240
0
This is the minimum delay between 2
load_add pulses.
Review chapter “Load
Shedding” for more details.
Load Subtract-Add Delay
min
0
120
0
This is the minimum delay required for a
load_add pulse after a load_substract
pulse.
Review chapter “Load Shedding”
for more details.
Mains Waiting Timer
sec
0
50000
30
This is the time between the mains
voltages and frequency entered within
the limits and the generator contactor is
deactivated.
Mains Connection
Topology
-
0
7
5
This is the connection topology of mains
voltages and CTs. Detailed
explanations are given in the chapter:
“TOPOLOGIES”.
0:
2 phase, 3 wire L1-L2
1:
2 phase, 3 wire L1-L3
2:
3 phase, 3 wire
3:
3 phase, 3 wire, 2CTs L1-L2
4:
3 phase, 3 wire, 2CTs L1-L3
5:
3 phase, 4 wire star
6:
3 phase, 4 wire delta
7:
single phase, 2 wire
Genset Connection
Topology
-
0
7
5
This is the connection topology of
genset voltages and CTs. Detailed
explanations are given in the chapter:
TOPOLOGIES.
0:
2 phase, 3 wire L1-L2
1:
2 phase, 3 wire L1-L3
2:
3 phase, 3 wire
3:
3 phase, 3 wire, 2CTs L1-L2
4:
3 phase, 3 wire, 2CTs L1-L3
5:
3 phase, 4 wire star
6:
3 phase, 4 wire delta
7:
single phase, 2 wire
16.2. ELECTRICAL PARAMETERS GROUP (continued)
Summary of Contents for D-200 MK2
Page 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Page 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Page 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...