D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 128 -
When necessary, the controller may be manually reset by holding the STOP button pressed for 30
seconds.
The manual reset will cause the hardware to be configured following new settings.
It is advised to proceed to a manual reset or power off/on cycle after every hardware configuration
modification.
Feature not applicable to this product.
In a manual genset, it is possible to reduce the current consumption of the unit down to true zero
Amperes, in order to prevent the battery from discharging.
For “zero power at rest operation”, an external relay and “wake-up” pushbutton is necessary.
A digital output should be set to ZERO POWER RELAY function. An external relay should be driven with
this digital output. The relay contact will feed the controller power supply.
Any digital output may be assigned as zero-power-relay output. Please refer to the relay function list for
the setup.
CONTROLLER
BAT+
OUTx
SUPPLY
The controller wakes-
up on applying the power through the “wake-up” pushbutton. Then it will
immediately activate the zero power output which will cause the zero power relay to feed the controller.
If the engine is not run, or if the engine stops, a timer of 5 minutes will be counted. At the expiration of the
counter, the controller will deenergize the zero power relay which will cut the power supply. The controller
will wait in a zero-power state until the wake-up pushbutton is depressed again.
25.24. ZERO POWER AT REST
25.23.-
25.22. RESETTING THE CONTROLLER
Wake-Up
pushbutton
Zero Power
Relay
Summary of Contents for D-200 MK2
Page 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Page 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Page 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...