D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 95 -
The unit has 6 digital inputs. Only parameters of one input are explained below. Other inputs have
identical parameter set.
The input name is freely programmable, thus the input can be adapted to any functionality through
programming.
Each sender has below programmable parameters:
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Input Function
-
0
99
Selects between predefined input
functions. Selected input name is
displayed in the line below.
If this parameter is set to 0 then the
input name string can be freely entered.
Action
-
0
3
0:
shutdown alarm
1:
loaddump alarm
2:
warning
3:
no fault condition from this input.
Sampling
-
0
3
0:
always
1:
on engine running
2:
after hold-off timer
3:
reserved
Latching
-
0
1
0:
non-latching. The fault disappears
when cause is removed.
1:
latching. The fault persists even if the
cause is removed. Requires manual
reset.
Contact type
-
0
1
0:
Normally open
1:
Normally closed
Switching
-
0
1
0:
Battery negative
1:
Battery positive
Response delay
-
0
3
0:
No delay
1:
Delayed (1sec)
2:
Delayed (10sec)
3:
Delayed (1800sec)
The input name entry is made through RainbowPlus
program only.
16.8. DIGITAL INPUT CONFIGURATION
Summary of Contents for D-200 MK2
Page 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Page 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Page 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...