Idle Speed (Run) Timer
sec
0
240
0
When the engine runs, the Idle output
relay function will be active during this
timer. While the IDLE output is active,
low voltage, low frequency and low rpm
checks are disabled.
Idle Speed (Stop) Timer
sec
0
240
0
Before the engine stops, the Idle output
relay function will be active during this
timer. While the IDLE output is active,
low voltage, low frequency and low rpm
checks are disabled.
Idle Holdoff Timer
sec
0
30
10
While the IDLE period is over, low
voltage, low frequency and low speed
checks are enabled after the expiration
of this timer.
Gas Solenoid Delay
sec
0
240
5
The gas solenoid of the gas engine (if
assigned by
Relay Definitions
) will be
opened after this delay during cranking.
Crank Cut Voltage
V-AC
0
65000
100
The crank relay output is deenergized
when the genset phase L1 voltage
reaches this limit.
Crank Cut Frequency
Hz
0
100
10
The crank relay output is deenergized
when the genset frequency reaches this
limit.
Crank Cut RPM
rpm
0
65000
500
The crank relay output is deenergized
when the engine rpm reaches this limit.
Crank Cut Charge
Voltage
V-DC
0
40
6
The crank relay output is deenergized
when the charge alternator voltage
reaches this limit.
Crank Cut with Oil
Pressure
-
0
1
0
0:
no crank cut with oil pressure
1:
cranking is cut when oil pressure
switch is open or the oil pressure
measured is above shutdown limit.
Crank Cut with Oil
Pressure Delay
sec
0
30
2
If crank cutting with oil pressure is
enabled, cranking is cut after this delay
when oil pressure switch is open or the
oil pressure measured is above
shutdown limit.
Charge Input Connected
-
0
1
0
0:
Crank cutting with charge input
disabled
1:
Crank cutting with charge input
enabled
Fuel Tank Capacity
Lt
0
65000
0
The full capacity of the fuel tank. If this
parameter is zero, the fuel quantity in
the tank is not displayed.
Fuel Consumption per
Hour
%
0
100
0.0
This parameter is the threshold for
sending FUEL THEFT and FUELLING
sms messages.
If this parameter is set to 0, then no
Fuel Theft and Fuelling sms messages
will be sent.
If SMS is required, set this parameter to
a value above the hourly fuel
consumption of the genset.
16.3. ENGINE PARAMETERS GROUP (continued)
Summary of Contents for D-200 MK2
Page 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Page 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Page 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...