3.3.1.1 STO Connectors
Item Position
on SAB
Description
Drawing/
pins
Ratings
STO
1 IN:
STO
Front
Used for STO
input voltage
1.
130BE393.10
+ STO –
Pins (left
to right):
STO+
STO-
Nominal voltage:
24 V DC
±
10%
Nominal current:
Depends on the
number of servo
drives in the
application.
Maximum current:
1 A
Maximum cross-
section:
1.5 mm
2
STO
2 IN:
STO
Front
Used for STO
input voltage
2.
STO
1 IN:
24 V
Front
These
connectors can
only be used
to make a
bridge to STO
1 IN: STO and
STO 2 IN: STO
if the STO
function is not
required in the
application.
This connector
cannot be
used for any
other function.
130BE396.10
+ 24V –
Pins (left
to right):
24+
24-
Nominal voltage:
24 V DC
±
10%
Nominal current:
1 A
Maximum cross-
section:
1.5 mm
2
STO
2 IN:
24 V
Front
ISD
Line
1:
STO
1
Underside Used for STO
output voltage
1.
130BE394.10
+ STO –
Pins (left
to right):
STO+
STO-
Nominal voltage:
24 V DC
±
10%
Nominal current:
Depends on the
number of servo
drives in the
application.
Maximum current:
1 A
Maximum cross-
section:
0.5 mm
2
ISD
Line
2:
STO
2
Underside Used for STO
output voltage
2.
Table 3.7 STO Connectors
3.3.1.2 Mains Connectors
Item
Description
Drawing/
pins
Ratings
AC
mains
supply
Used to connect
L1/L2/L3
130BE388.10
L1
L2
L3
Pins (left
to right):
L1
L2
L3
Nominal voltage:
400–480 V AC
Nominal current:
12.5 A
Maximum cross-section:
4 mm
2
Mains
PE
The PE screw is
used to connect
the protective
earth, see
.
–
Cross-section:
10 mm
2
See
for
further information.
Table 3.8 Mains Connectors
130BE706.10
1
1
PE screw
Illustration 3.9 PE Screw