Frequency Converter, P22K, T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
36
240
0.244
0.608
1.993
136
240
0.560
0.580
0.832
150
240
0.720
0.574
0.661
Frequency Converter, P30K, T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
15
240
0.194
0.626
2.581
50
240
0.252
0.574
1.929
150
240
0.444
0.538
0.977
Frequency Converter, P37K, T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
240
0.300
0.598
1.593
100
240
0.536
0.566
0.843
150
240
0.776
0.546
0.559
Frequency Converter, P45K, T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
240
0.300
0.598
1.593
100
240
0.536
0.566
0.843
150
240
0.776
0.546
0.559
Frequency Converter, P1K5, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
400
0.640
0.690
0.862
50
400
0.470
0.985
0.985
150
400
0.760
1.045
0.947
Frequency Converter, P4K0, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
400
0.172
0.890
4.156
50
400
0.310
2.564
150
400
0.370
1.190
1.770
Frequency Converter, P7K5, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
400
0.04755
0.739
8.035
50
400
0.207
1.040
4.548
150
400
0.6742
1.030
2.828
8 General Specifications and Troubleshooting
VLT
®
HVAC Drive Design Guide
176
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark