380-480 V, frame sizes D, E and F
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V, or 600V depending on the
drive voltage rating. With the proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
Size/
Type
Bussmann
E1958
JFHR2**
Bussmann
E4273
T/JDDZ**
SIBA
E180276
JFHR2
LittelFuse
E71611
JFHR2**
Ferraz-
Shawmut
E60314
JFHR2**
Bussmann
E4274
H/JDDZ**
Bussmann
E125085
JFHR2*
Internal
Option
Bussmann
P110
FWH-
300
JJS-
300
2061032.315
L50S-300
A50-P300
NOS-
300
170M3017
170M3018
P132
FWH-
350
JJS-
350
2061032.35
L50S-350
A50-P350
NOS-
350
170M3018
170M3018
P160
FWH-
400
JJS-
400
2061032.40
L50S-400
A50-P400
NOS-
400
170M4012
170M4016
P200
FWH-
500
JJS-
500
2061032.50
L50S-500
A50-P500
NOS-
500
170M4014
170M4016
P250
FWH-
600
JJS-
600
2062032.63
L50S-600
A50-P600
NOS-
600
170M4016
170M4016
Table 5.8: Frame size D, Line fuses, 380-480 V
Size/Type
Bussmann PN*
Rating
Ferraz
Siba
P315
170M4017
700 A, 700 V
6.9URD31D08A0700
20 610 32.700
P355
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P400
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P450
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
Table 5.9: Frame size E, Line fuses, 380-480 V
Size/Type
Bussmann PN*
Rating
Siba
Internal Bussmann Option
P500
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P560
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P630
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
P710
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
P800
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
P1M0
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
Table 5.10: Frame size F, Line fuses, 380-480 V
Size/Type
Bussmann PN*
Rating
Siba
P500
170M8611
1100 A, 1000 V
20 781 32.1000
P560
170M8611
1100 A, 1000 V
20 781 32.1000
P630
170M6467
1400 A, 700 V
20 681 32.1400
P710
170M6467
1400 A, 700 V
20 681 32.1400
P800
170M8611
1100 A, 1000 V
20 781 32.1000
P1M0
170M6467
1400 A, 700 V
20 681 32.1400
Table 5.11: Frame size F, Inverter module DC Link Fuses, 380-480 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use
**Any minimum 500 V UL listed fuse with associated current rating may be used to meet UL requirements.
525-690 V, frame sizes D, E and F
Size/Type
Bussmann
E125085
JFHR2
Amps
SIBA
E180276
JFHR2
Ferraz-Shawmut
E76491
JFHR2
Internal
Option
Bussmann
P45K
170M3013
125
2061032.125
6.6URD30D08A0125
170M3015
P55K
170M3014
160
2061032.16
6.6URD30D08A0160
170M3015
P75K
170M3015
200
2061032.2
6.6URD30D08A0200
170M3015
P90K
170M3015
200
2061032.2
6.6URD30D08A0200
170M3015
P110
170M3016
250
2061032.25
6.6URD30D08A0250
170M3018
P132
170M3017
315
2061032.315
6.6URD30D08A0315
170M3018
P160
170M3018
350
2061032.35
6.6URD30D08A0350
170M3018
P200
170M4011
350
2061032.35
6.6URD30D08A0350
170M5011
P250
170M4012
400
2061032.4
6.6URD30D08A0400
170M5011
P315
170M4014
500
2061032.5
6.6URD30D08A0500
170M5011
P400
170M5011
550
2062032.55
6.6URD32D08A550
170M5011
Table 5.12: Frame size D, 525-690 V
VLT
®
HVAC Drive Design Guide
5 How to Install
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark
99