Mains Supply 3 x 525- 690 VAC
P500
P560
P630
Typical Shaft output at 550 V
[kW]
400
450
500
Typical Shaft output at 575 V
[HP]
500
600
650
Typical Shaft output at 690 V
[kW]
500
560
630
Enclosure IP21
E1
E1
E1
Enclosure
IP54
E1
E1
E1
Enclosure IP00
E2
E2
E2
Output current
Continuous
(at 550 V) [A]
523
596
630
Intermittent (60 sec overload)
(at 550 V) [A]
575
656
693
Continuous
(at 575/ 690 V) [A]
500
570
630
Intermittent (60 sec overload)
(at 575/ 690 V) [A]
550
627
693
Continuous KVA
(at 550 V) [KVA]
498
568
600
Continuous KVA
(at 575 V) [KVA]
498
568
627
Continuous KVA
(at 690 V) [KVA]
598
681
753
Max. input current
Continuous
(at 550 V ) [A]
504
574
607
Continuous
(at 575 V) [A]
482
549
607
Continuous
(at 690 V) [A]
482
549
607
Max. cable size, mains, motor
and load share [mm
2
(AWG)]
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses [A]
1
700
900
900
Estimated power loss
at rated max. load [W]
4)
, 600
V
6903
8343
9244
Estimated power loss
at rated max. load [W]
4)
, 690
V
7249
8727
9673
Weight,
enclosure IP21, IP 54 [kg]
263
272
313
Weight,
enclosure IP00 [kg]
221
236
277
Efficiency
4)
0.98
Output
frequency
0 - 500 Hz
Heatsink overtemp. trip
85
°
C
Power card ambient trip
68
°
C
8 General Specifications and Troubleshooting
VLT
®
HVAC Drive Design Guide
166
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark
8