This alarm/ warning could also occur should the brake resistor overheat.
Terminal 104 to 106 are available as brake resistor. Klixon inputs, see
section Brake Resistor Temperature Switch.
WARNING/ALARM 28, Brake check failed
Brake resistor fault: the brake resistor is not connected or not working.
Check par. 2-15
Brake Check
.
ALARM 29, Heatsink temp
The maximum temperature of the heatsink has been exceeded. The tem-
perature fault will not be reset until the temperature falls below a defined
heatsink temperature. The trip and reset point are different based on the
drive power size.
Troubleshooting:
Ambient temperature too high.
Too long motor cable.
Incorrect clearance above and below the drive.
Dirty heatsink.
Blocked air flow around the drive.
Damaged heatsink fan.
For the D, E, and F Frame Drives, this alarm is based on the temperature
measured by the heatsink sensor mounted inside the IGBT modules. For
the F Frame drives, this alarm can also be caused by the thermal sensor
in the Rectifier module.
Troubleshooting:
Check fan resistance.
Check soft charge fuses.
IGBT thermal sensor.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the motor is miss-
ing.
Turn off the frequency converter and check motor phase U.
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and the motor is missing.
Turn off the frequency converter and check motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the motor is miss-
ing.
Turn off the frequency converter and check motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time period. Let unit
cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The fieldbus on the communication option card is not working.
WARNING/ALARM 35, Out of frequency range:
This warning is active if the output frequency has reached the high limit
(set in par. 4-53) or low limit (set in par. 4-52). In
Process Control, Closed
Loop
(. 1-00) this warning is displayed.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to the frequency
converter is lost and par. 14-10
Mains Failure
is NOT set to OFF. Check
the fuses to the frequency converter
ALARM 38, Internal fault
It may be necessary to contact your Danfoss supplier. Some typical alarm
messages:
0
Serial port cannot be initialized. Serious hardware failure
256-258 Power EEPROM data is defect or too old
512
Control board EEPROM data is defect or too old
513
Communication time out reading EEPROM data
514
Communication time out reading EEPROM data
515
Application Orientated Control cannot recognize the EE-
PROM data
516
Cannot write to the EEPROM because a write command
is on progress
517
Write command is under time out
518
Failure in the EEPROM
519
Missing or invalid Barcode data in EEPROM
783
Parameter value outside of min/max limits
1024-127
9
A can-telegram that has to be sent, couldn't be sent
1281
Digital Signal Processor flash timeout
1282
Power micro software version mismatch
1283
Power EEPROM data version mismatch
1284
Cannot read Digital Signal Processor software version
1299
Option SW in slot A is too old
1300
Option SW in slot B is too old
1301
Option SW in slot C0 is too old
1302
Option SW in slot C1 is too old
1315
Option SW in slot A is not supported (not allowed)
1316
Option SW in slot B is not supported (not allowed)
1317
Option SW in slot C0 is not supported (not allowed)
1318
Option SW in slot C1 is not supported (not allowed)
1379
Option A did not respond when calculating Platform Ver-
sion.
1380
Option B did not respond when calculating Platform Ver-
sion.
1381
Option C0 did not respond when calculating Platform
Version.
1382
Option C1 did not respond when calculating Platform
Version.
1536
An exception in the Application Orientated Control is
registered. Debug information written in LCP
1792
DSP watchdog is active. Debugging of power t data Mo-
tor Orientated Control data not transferred correctly
2049
Power data restarted
2064-207
2
H081x: option in slot x has restarted
2080-208
8
H082x: option in slot x has issued a powerup-wait
2096-210
4
H083x: option in slot x has issued a legal powerup-wait
2304
Could not read any data from power EEPROM
2305
Missing SW version from power unit
2314
Missing power unit data from power unit
2315
Missing SW version from power unit
2316
Missing io_statepage from power unit
2324
Power card configuration is determined to be incorrect
at power up
2330
Power size information between the power cards does
not match
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP (state running)
2816
Stack overflow Control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP Stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool to small
3072-512
2
Parameter value is outside its limits
5123
Option in slot A: Hardware incompatible with Control
board hardware
5124
Option in slot B: Hardware incompatible with Control
board hardware
5125
Option in slot C0: Hardware incompatible with Control
board hardware
5126
Option in slot C1: Hardware incompatible with Control
board hardware
5376-623
1
Out of memory
8 General Specifications and Troubleshooting
VLT
®
HVAC Drive Design Guide
190
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark
8