Size/Type
Bussmann PN*
Rating
Ferraz
Siba
P450
170M4017
700 A, 700 V
6.9URD31D08A0700
20 610 32.700
P500
170M4017
700 A, 700 V
6.9URD31D08A0700
20 610 32.700
P560
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P630
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
Table 5.13: Frame size E, 525-690 V
Size/Type
Bussmann PN*
Rating
Siba
Internal Bussmann Option
P710
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P800
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P900
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P1M0
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P1M2
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
P1M4
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
Table 5.14: Frame size F, Line fuses, 525-690 V
Size/Type
Bussmann PN*
Rating
Siba
P710
170M8611
1100 A, 1000 V
20 781 32. 1000
P800
170M8611
1100 A, 1000 V
20 781 32. 1000
P900
170M8611
1100 A, 1000 V
20 781 32. 1000
P1M0
170M8611
1100 A, 1000 V
20 781 32. 1000
P1M2
170M8611
1100 A, 1000 V
20 781 32. 1000
P1M4
170M8611
1100 A, 1000 V
20 781 32.1000
Table 5.15: Frame size F, Inverter module DC Link Fuses, 525-690 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use.
Suitable for use on a circuit capable of delivering not more than 100 000 rms symmetrical amperes, 500/600/690 Volts maximum when protected by the
above fuses.
Supplementary fuses
Frame size
Bussmann PN*
Rating
D, E and F
KTK-4
4 A, 600 V
Table 5.16: SMPS Fuse
Size/Type
Bussmann PN*
LittelFuse
Rating
P110-P315, 380-480 V
KTK-4
4 A, 600 V
P45K-P500, 525-690 V
KTK-4
4 A, 600 V
P355-P1M0, 380-480 V
KLK-15
15A, 600 V
P560-P1M4, 525-690 V
KLK-15
15A, 600 V
Table 5.17: Fan Fuses
Size/Type
Bussmann PN*
Rating
Alternative Fuses
P500-P1M0, 380-480 V
2.5-4.0 A
LPJ-6 SP or SPI
6 A, 600 V
Any listed Class J Dual Ele-
ment, Time Delay, 6A
P710-P1M4, 525-690 V
LPJ-10 SP or SPI
10 A, 600 V
Any listed Class J Dual Ele-
ment, Time Delay, 10 A
P500-P1M0, 380-480 V
4.0-6.3 A
LPJ-10 SP or SPI
10 A, 600 V
Any listed Class J Dual Ele-
ment, Time Delay, 10 A
P710-P1M4, 525-690 V
LPJ-15 SP or SPI
15 A, 600 V
Any listed Class J Dual Ele-
ment, Time Delay, 15 A
P500-P1M0, 380-480 V
6.3 - 10 A
LPJ-15 SP or SPI
15 A, 600 V
Any listed Class J Dual Ele-
ment, Time Delay, 15 A
P710-P1M4, 525-690 V
LPJ-20 SP or SPI
20 A, 600 V
Any listed Class J Dual Ele-
ment, Time Delay, 20A
P500-P1M0, 380-480 V
10 - 16 A
LPJ-25 SP or SPI
25 A, 600 V
Any listed Class J Dual Ele-
ment, Time Delay, 25 A
P710-P1M4, 525-690 V
LPJ-20 SP or SPI
20 A, 600 V
Any listed Class J Dual Ele-
ment, Time Delay, 20 A
Table 5.18: Manual Motor Controller Fuses
5 How to Install
VLT
®
HVAC Drive Design Guide
100
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark
5