5.4.3 F Frame circuit breakers
Frame size
Power & Voltage
Type
F3
P500 380-480V & P710-P800 525-690V
Merlin Gerin NPJF36120U31AABSCYP
F3
P630-P710 380-480V & P900 525-690V
Merlin Gerin NRJF36200U31AABSCYP
F4
P800 380-480V & P1M0-P1M2 525-690V
Merlin Gerin NRJF36200U31AABSCYP
F4
P1M0 380-480V
Merlin Gerin NRJF36250U31AABSCYP
5.4.4 F Frame Mains Contactors
Frame size
Power & Voltage
Type
F3
P500-P560 380-480V & P710-P900 525-690V
Eaton XTCE650N22A
F3
P630 380-480V
Eaton XTCE820N22A
F3
P710 380-480V
Eaton XTCEC14P22B
F4
P1M0 525-690V
Eaton XTCE820N22A
F4
P800-P1M0 380-480V & P1M4 525-690V
Eaton XTCEC14P22B
5.4.5 Brake Resistor Temperature Switch
Frame size D-E-F
Torque: 0.5-0.6 Nm (5 in-lbs)
Screw size: M3
This input can be used to monitor the temperature of an externally connected brake resistor. If the input between 104 and 106 is established, the
frequency converter will trip on warning / alarm 27, “Brake IGBT”. If the connection is closed between 104 and 105, the frequency converter will trip on
warning / alarm 27, “Brake IGBT”.
Normally closed: 104-106 (factory installed jumper)
Normally open: 104-105
Terminal No.
Function
106, 104, 105
Brake resistor temperature switch.
If the temperature of the brake resistor gets too high
and the thermal switch drops out, the frequency con-
verter will stop braking. The motor will start coasting.
A KLIXON switch must be installed that is `normally
closed'. If this function is not used, 106 and 104 must
be short-circuited together.
5.4.6 External Fan Supply
Frame size D-E-F
In case the frequency converter is supplied by DC or if the fan must run independently of the power supply, an external power supply can be applied.
The connection is made on the power card.
Terminal No.
Function
100, 101
102, 103
Auxiliary supply S, T
Internal supply S, T
5 How to Install
VLT
®
HVAC Drive Design Guide
108
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark
5