8 General Specifications and Troubleshooting
8.1 Mains Supply Tables
Mains supply 200 - 240 VAC
-
Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P3K7
3.7
IP 20 / Chassis
(A2+A3 may be converted to IP21 using a conversion kit. (Please see
also items
Mechanical mounting
in Operating Instructions and
IP 21/
Type 1 Enclosure kit
in the Design Guide.))
A2
A2
A2
A3
A3
IP 55 / NEMA 12
A5
A5
A5
A5
A5
IP 66 / NEMA 12
A5
A5
A5
A5
A5
Typical Shaft Output [HP] at 208 V
1.5
2.0
2.9
4.0
4.9
Output current
Continuous
(3 x 200-240 V ) [A]
6.6
7.5
10.6
12.5
16.7
Intermittent
(3 x 200-240 V ) [A]
7.3
8.3
11.7
13.8
18.4
Continuous
kVA (208 V AC) [kVA]
2.38
2.70
3.82
4.50
6.00
Max. cable size:
(mains, motor, brake)
[mm
2
/AWG]
2)
4/10
Max. input current
Continuous
(3 x 200-240 V ) [A]
5.9
6.8
9.5
11.3
15.0
Intermittent
(3 x 200-240 V ) [A]
6.5
7.5
10.5
12.4
16.5
Max. pre-fuses
1)
[A]
20
20
20
32
32
Environment
Estimated power loss
at rated max. load [W]
4)
63
82
116
155
185
Weight enclosure IP20 [kg]
4.9
4.9
4.9
6.6
6.6
Weight enclosure IP21 [kg]
5.5
5.5
5.5
7.5
7.5
Weight enclosure IP55 [kg]
13.5
13.5
13.5
13.5
13.5
Weight enclosure IP 66 [kg]
13.5
13.5
13.5
13.5
13.5
Efficiency
3)
0.96
0.96
0.96
0.96
0.96
Table 8.1: Mains Supply 200 - 240 VAC
VLT
®
HVAC Drive Design Guide
8 General Specifications and Troubleshooting
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark
155