Mains Supply 3 x 525- 690 VAC
P710
P800
P900
P1M0
P1M2
P1M4
Typical Shaft output
at 550 V [kW]
560
670
750
850
1000
1100
Typical Shaft output
at 575 V [HP]
750
950
1050
1150
1350
1550
Typical Shaft output
at 690 V [kW]
710
800
900
1000
1200
1400
Enclosure IP21, 54
without/ with options
cabinet
F1/ F3
F1/ F3
F1/ F3
F2/ F4
F2/ F4
F2/F4
Output current
Continuous
(at 550 V) [A]
763
889
988
1108
1317
1479
Intermittent (60 s
overload, at 550 V)
[A]
839
978
1087
1219
1449
1627
Continuous
(at 575/ 690 V) [A]
730
850
945
1060
1260
1415
Intermittent (60 s
overload, at 575/690
V) [A]
803
935
1040
1166
1386
1557
Continuous KVA
(at 550 V) [KVA]
727
847
941
1056
1255
1409
Continuous KVA
(at 575 V) [KVA]
727
847
941
1056
1255
1409
Continuous KVA
(at 690 V) [KVA]
872
1016
1129
1267
1506
1691
Max. input current
Continuous
(at 550 V ) [A]
743
866
962
1079
1282
1440
Continuous
(at 575 V) [A]
711
828
920
1032
1227
1378
Continuous
(at 690 V) [A]
711
828
920
1032
1227
1378
Max. cable size,mo-
tor [mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable
size,mains [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
8x456
8x900 mcm
Max. cable size, load-
sharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size,
brake [mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external pre-
fuses [A]
1)
1600
2000
2500
Est. power loss
at rated max. load
[W]
4)
, 600 V, F1 & F2
10771
12272
13835
15592
18281
20825
Est. power loss
at rated max. load
[W]
4)
, 690 V, F1 & F2
11315
12903
14533
16375
19207
21857
Max added losses of
Circuit Breaker or
Disconnect & Contac-
tor, F3 & F4
427
532
615
665
863
1044
Max Panel Options
Losses
400
Weight,enclo-
sure IP21, IP 54 [kg]
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
1280/1575
Weight, Rectifier
Module [kg]
102
102
102
136
136
136
Weight, Inverter
Module [kg]
102
102
136
102
102
136
Efficiency
4)
0.98
Output frequency
0-500 Hz
Heatsink overtemp.
trip
85
°
C
Power card amb. trip
68
°
C
1) For type of fuse see section
Fuses.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerence relates to variety in voltage and cable
conditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss
in the frequency converter and opposite. If the switching frequency is increased comed to the default setting, the power losses may rise sig-
VLT
®
HVAC Drive Design Guide
8 General Specifications and Troubleshooting
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark
167