Motor Set-up
The Quick Menu Motor Set-up guides through the needed
motor parameters.
No & Name
Range
Default
Function
0-03 Regional
Settings
[0] Interna-
tional
[1] US
0
1-20 Motor
power
0.12-110kW/
0.16-150Hp
Size related
Enter motor
power from
nameplate data
1-22 Motor
Voltage
50.0 - 1000.0V Size related
Enter motor
voltage from
nameplate data
1-23 Motor
Frequency
20.0 - 400.0Hz Size related
Enter motor
frequency from
nameplate data
1-24 Motor
Current
0.01 -
10000.00A
Size related
Enter motor
current from
nameplate data
1-25 Motor
Nominal Speed
100.0 - 9999.0
RPM
Size related
Enter motor
nominal speed
from nameplate
data
4-12 Motor
Speed Low
Limit [Hz]
0.0 - Hz
0.0 Hz
Enter the
minimum limit for
low speed
4-14 Motor
Speed High
Limit [Hz]
0-HZ
65
3-41 Ramp 1
Ramp up time
0.05 - 3600.0 s Size related
Ramp up time
from 0 to rated
motor frequency
par. 1-23
3-42 Ramp 1
Ramp down
time
0.05 - 3600.0 s Size related
Ramp down time
from rated motor
frequency par.
1-23 to 0
1-73 Flying
Start
[0] Disabled
[1] Enabled
0
Select Enable to
enable the drive
to catch a
spinning motor
Changes Made
Changes Made lists all parameters changed since factory
setting. Only the changed parameters in current edit-setup
are listed in changes made.
If the parameter's value is changed back to factory setting's
value from another different value, the parameter will NOT
be listed in Changes Made.
1.
Press [MENU] key to enter the Quick Menu until
indicator in display is placed above Quick Menu.
2.
Press [
▲
] [
▼
] to select either FC 101 wizard, closed
loop setup, motor setup or changes made, then
press [OK].
3.
Press [
▲
] [
▼
] to browse through the parameters in
the Quick Menu.
4.
Press [OK] to select a parameter.
5.
Press [
▲
] [
▼
] to change the value of a parameter
setting.
6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter “Status”, or press
[Menu] once to enter “Main Menu”.
The Main Menu accesses all parameters.
1.
Press [MENU] key until indicator in display is placed
above “Main Menu”.
2.
Use [
▲
] [
▼
] to browse through the parameter
groups.
3.
Press [OK] to select a parameter group.
4.
Use [
▲
] [
▼
] to browse through the parameters in
the specific group.
5.
Press [OK] to select the parameter.
6.
Use [
▲
] [
▼
] to set/change the parameter value.
Quick Guide
VLT HVAC Basic Drive FC 101 Quick Guide
MG.18.A1.02 - VLT
®
is a registered Danfoss trademark
17