Parameter Overview
1-72 Start Function
[0] DC Hold/delay time
*[2] Coast/delay time
1-73 Flying Start
*[0] Disabled
[1] Enabled
1-8* Stop Adjustments
1-80 Function at Stop
*[0] Coast
[1] DC hold/MotorPreheat
1-82 Min Speed for Function at Stop
[Hz]
0.0 - 20.0Hz, * 0.0
1-9* Motor Temperature
1-90 Motor Thermal Protection
*[0] No protection
[1] Thermistor warning
[2] Thermistor trip
[3] ETR warning 1
[4] ETR trip 1
1-93 Thermistor Resource
*[0] None
[1] Analog input 53
[6] Digital input 29
2-** Brakes
2-0* DC-Brake
2-00 DC Hold/Motor Preheat Current
0 - 160%, * 50
2-01 DC Brake Current
0 - 150%, * 50
2-02 DC Braking Time
0.0 - 60.0s, * 10.0
2-04 DC Brake Cut In Speed
0.0 - 400.0Hz, * 0.0
2-1* Brake Energy Funct.
2-17 Over-voltage Control
[0] Disabled
*[2] Enabled
2-19 Over-voltage Gain
0 - 200%, * 100
3-** Reference / Ramps
3-0* Reference Limits
3-02 Minimum Reference
(-4999.000) - 4999.000, * 0.000
3-03 Maximum Reference
(-4999.000) - 4999.000, * 50.000
3-1* References
3-10 Preset Reference
-100.00 - 100.00%, * 0.00
3-11 Jog Speed [Hz]
0.0 - 400.0Hz, * 5.0
3-14 Preset Relative Reference
-100.00 - 100.00, * 0.00
3-15 Reference Resource 1
[0] No function
*[1] Analog in 53
[2] Analog in 54
[11] Local bus reference
3-16 Reference 2 Resource
[0] No function
[1] Analog in 53
*[2] Analog in 54
[11] Local bus reference
3-17 Reference 3 Resource
[0] No function
[1] Analog in 53
[2] Analog in 54
*[11] Local bus reference
3-4* Ramp 1
3-41 Ramp 1 Ramp up Time
0.05 - 3600.00s, *3.00
3-42 Ramp 1 Ramp Down Time
0.05 - 3600.00s, *3.00
3-5* Ramp 2
3-51 Ramp 2 Ramp up Time
0.05 - 3600.00s, *3.00
3-52 Ramp 2 Ramp down Time
0.05 - 3600.00s, *3.00
3-8* Other Ramps
3-80 Jog Ramp Time
0.05 - 3600.00s, *(3.00)
3-81 Quick Stop Ramp Time
0.05 - 3600.00s, *3.00
4-** Limits / Warnings
4-1* Motor Limits
4-10 Motor Speed Direction
[0] Clockwise
*[2] Both directions
4-12 Motor Speed Low Limit [Hz]
0.0 - 400.0, * 0.0Hz
4-14 Motor Speed High Limit
[Hz]
0.1 - 400.0, * 65.0Hz
4-18 Current Limit
0 - 800%, * 110
4-19 Max Output Frequency
0.0 - 400.0Hz, * 65.0
4-5* Adj. Warnings
4-50 Warning Current Low
0.00 - 194.00A, * 0.00
4-51 Warning Current High
0.00 - 194.00A, * 194.00
4-58 Missing Motor Phase
Function
[0] Off
*[1] On
4-6* Speed Bypass
4-61 Bypass Speed From [Hz]
0.0 - 400.0, * 0.0
4-63 Bypass Speed To [Hz]
0.0 - 400.0, * 0.0
4-64 Semi-Auto Bypass Set-up
*[0] Off
[1] Enable
5-** Digital In/Out
5-0* Digital I/O mode
5-00 Digital Input Mode
*[0] PNP
[1] NPN
5-03 Digital Input 29 Mode
*[0] PNP
[1] NPN
5-1* Digital Inputs
5-10 Terminal 18 Digital Input
[0] No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
*[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire mode
[52] Run permissive
[53] Hand Start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
5-11 Terminal 19 Digital Input
See par. 5-10, *[0] No operation
5-12 Terminal 27 Digital Input
See par. 5-10, *[2] Coast inverse
5-13 Terminal 29 Digital Input
See par. 5-10, *[14 Jog]
5-3* Digital Outputs
5-4* Relays
5-40 Function Relay
*[0] No operation
[1] Control ready
[2] Drive ready
[3] Drive ready/remote control
[4] Enable / no warning
[5] VLT running
[6] Running / no warning
[7] Run in range/no warning
[8] Run on ref/no warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
[14] Above current, high
[21] Thermal warning
[22] Ready, no thermal warning
[23] Remote, ready, no thermal
warning
[24] Ready, Voltage OK
[25] Reverse
[26] Bus OK
[35] External Interlock
[36] Control word bit 11
[37] Control word bit 12
[45] Bus Control
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic rule 0
71] Logic rule 1
[72] Logic rule 2
[73] Logic rule 3
[74] Logic rule 4
[75] Logic rule 5
[80] SL digital output A
[81] SL digital output B
[82] SL digital output C
[83] SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
5-5* Pulse Input
5-9* Bus Controlled
5-90 Digital and Relay Bus Control
0 - 0xFFFFFFFF, * 0
6-** Analog In/Out
6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
1 - 99s, * 10