All inputs, outputs, circuits, DC supplies and relay contacts
are galvanically isolated from the supply voltage (PELV) and
other high-voltage terminals.
Surroundings:
Enclosure
IP20
Enclosure kit available
IP21, TYPE 1
Vibration test
1.0g
Max. relative humidity
5% - 95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated (standard) frame H1-H5
Class 3C3
Aggressive environment (IEC 60721-3-3), non-coated frame H6-H10
Class 3C2
Aggressive environment (IEC 60721-3-3), coated (optional) frame H6-H10
Class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
See max. output current at 40/50
°
C in the tables mains supply
Derating for high ambient temperature, see section on
special conditions
Minimum ambient temperature during full-scale operation
0
°
C
Minimum ambient temperature at reduced performance, enclosure frame H1-H5
-20
°
C
Minimum ambient temperature at reduced performance, enclosure frame H6-H10
-10
°
C
Temperature during storage/transport
-30 - +65/70
°
C
Maximum altitude above sea level without derating
1000m
Maximum altitude above sea level with derating
3000m
Derating for high altitude, see section on special conditions
Safety standards
EN/IEC 61800-5-1, UL 508C
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
1.8 Special Conditions
1.8.1 Derating for Ambient Temperature
The ambient temperature measured over 24 hours should be
at least 5
°
C lower than the max. ambient temperature. If the
frequency converter is operated at high ambient
temperature, the continuous output current should be
decreased.
1.8.2 Derating for Low Air Pressure
The cooling capability of air is decreased at low air pressure.
For altitudes above 2000m, please contact Danfoss regarding
PELV. Below 1000m altitude no de-rating is necessary, but
above 1000m the ambient temperature or the maximum
output current should be decreased. Decrease the output by
1% per 100m altitude above 1000m or reduce the max.
ambient temperature by 1 degree per 200m.
1.9 Options for VLT HVAC Basic Drive FC 101