
Closed Loop Set-up Wizard
No & Name
Range
Default
Function
0-03 Regional Settings
[0] International
[1] US
0
1-20 Motor power
0.09-110kW
Size related Enter motor power from nameplate data
1-22 Motor Voltage
50.0 - 1000.0V
Size related Enter motor voltage from nameplate data
1-23 Motor Frequency
20.0 - 400.0Hz
Size related Enter motor frequency from nameplate data
1-24 Motor Current
0.01 - 10000.00A
Size related Enter motor current from nameplate data
1-25 Motor Nominal Speed
100.0 - 9999.0RPM Size related Enter motor nominal speed from nameplate data
4-12 Motor Speed Low Limit [Hz]
0.0 - Hz
0.0 Hz
Enter the minimum limit for low speed
4-14 Motor Speed High Limit [Hz]
0-Hz
65Hz
3-41 Ramp 1 Ramp up time
0.05 - 3600.0 s
3
Ramp up time from 0 to rated motor frequency par. 1-23
3-42 Ramp 1 Ramp down time
0.05 - 3600.0 s
3
Ramp down time form rated motor frequency par. 1-23 to 0
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select Enable to enable the drive to catch a spinning motor
3-02 Minimum Reference
-4999-4999
0
The minimum reference is the lowest value obtainable by summing all
references
3-03 Maximum Reference
-4999-4999
50
The maximum reference is the highest value obtainable by summing all
references
3-10 Preset Reference
-100-100%
0
Enter the set point
6-19 Terminal 53 mode
[0] Current
[1] Voltage
1
Select if terminal 53 is used for current- or voltage input
6-10 Terminal 53 Low Voltage
0-10V
0.07V
Enter the voltage that corresponds to the low reference value
6-11 Terminal 53 High Voltage
0-10V
10V
Enter the voltage that corresponds to the low high reference value
6-12 Terminal 53 Low Current
0-20mA
4
Enter the current that corresponds to the high reference value
6-13 Terminal 53 High Current
0-20mA
20
Enter the current that corresponds to the high reference value
6-14 Terminal 53 Low Ref./Feedb.
Value
-4999-4999
0
Enter the feedback value that corresponds to the voltage or current set
in par. 6-10/6-12
6-15 Terminal 53 High Ref./Feedb.
Value
-4999-4999
50
Enter the feedback value that corresponds to the voltage or current set
in par. 6-11/6-13
6-16 Terminal 53 Filter Time
Constant
0-10 s
0.01
Enter the filter time comstant
20-81 PI Normal/Inverse control
[0] Normal
[1] Inverse
0
Select
Normal
[0] to set the process control to increase the output
speed when the process error is positive. Select
Inverse
[1] to reduce the
output speed.
20-83 PI Start Speed
0-200Hz
0
Enter the motor speed to be attained as a start signal for
commencement of PI control
20-93 PI Proportional Gain
0-10
0.01
Enter the process controller proportional gain. Quick control is obtained
at high amplification. However if amplification os too great, the process
may become unstable
1-29 Automatic Motor Adaption
(AMA)
Off
Performing an AMA optimizes motor performance
Quick Guide
VLT HVAC Basic Drive FC 101 Quick Guide
16
MG.18.A1.02 - VLT
®
is a registered Danfoss trademark
1
1