The FC 101 Start-up Wizard for Open Loop Applications
No & Name
Range
Default
Function
0-03 Regional Settings
[0] International
[1] US
0
1-20
Motor power
0.12-110kW/0.16-150Hp Size related Enter motor power from nameplate data
1-22 Motor Voltage
50.0 - 1000.0V
Size related Enter motor voltage from nameplate data
1-23 Motor Frequency
20.0 - 400.0Hz
Size related Enter motor frequency from nameplate data
1-24 Motor Current
0.01 - 10000.00A
Size related Enter motor current from nameplate data
1-25 Motor Nominal Speed
100.0 - 9999.0 RPM
Size related Enter motor nominal speed from nameplate data
4-12 Motor Speed Low Limit [Hz]
0.0 - Hz
0 Hz
Enter the minimum limit for low speed
4-14 Motor Speed High Limit [Hz]
0.0 - Hz
65 Hz
Enter the maximum limit for high speed
3-41 Ramp 1 Ramp up time
0.05 - 3600.0 s
3
Ramp up time from 0 to rated motor frequency par. 1-23
3-42 Ramp 1 Ramp down time
0.05 - 3600.0 s
3
Ramp down time from rated motor frequency par. 1-23 to 0
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select Enable to enable the drive to catch a spinning motor
6-19 Terminal 53 mode
[0] Current
[1] Voltage
1
Select if terminal 53 is used for current- or voltage input
6-10 Terminal 53 Low Voltage
0-10V
0.07V
Enter the voltage that corresponds to the low reference value
6-11 Terminal 53 High Voltage
0-10V
10V
Enter the voltage that corresponds to the high reference value
6-12 Terminal 53 Low Current
0-20mA
4
Enter the current that corresponds to the low reference value
6-13 Terminal 53 High Current
0-20mA
20
Enter the current that corresponds to the high reference value
3-02 Minimum Reference
-4999-4999
0
The minimum reference is the lowest value obtainable by
summing all references
3-03 Maximum Reference
-4999-4999
50
The maximum reference is the lowest obtainable by summing all
references
5-40 Function Relay
[0] Function relay See
5-40 Function Relay
No function Select the function to control output relay 1
5-40 Function Relay
[1] Function relay See
5-40 Function Relay
No function Select the function to control output relay 2
1-29 Automatic Motor Adation
Off
Performing an AMA optimizes motor performance