1.7 General Specifications
1.7.1 Mains Supply 3 x 200-240VAC
Frequency converter
PK25
PK37
PK75
P1K5
P2K2
P3K7
P5K5
P7K5
P11K
Typical shaft output (KW)
0.25
0.37
0.75
1.5
2.2
3.7
5.5
7.5
11
Typical shaft output (HP)
0.33
0.5
1
2
3
5
7.5
10
15
IP20 frame
H1
H1
H1
H1
H2
H3
H4
H4
H5
Max. cable size in terminals (mains,
motor) [mm
2
/AWG]
4/10
4/10
4/10
4/10
4/10
4/10
16/6
16/6
16/6
Output current
RELAY 2
130BB632.10
40
°
C ambient temperature
Continuous
(3x200-240V) [A]
1.5
2.2
4.2
6.8
9.6
15.2
22
28
42
Intermittent
(3x200-240V)[A]
1.7
2.4
4.6
7.5
10.6
16.7
24.2
30.8
46.2
Max. input current
RELAY 2
130BB633.10
40
°
C ambient temperature
Continuous
(3x200-240V) [A]
1.1
1.6
2.8
5.6
8.8/7.2
14.1/12
21/18
28.3/24
41/38.2
Intermittent
(3x200-240V)[A]
1.2
1.8
3.1
6.2
9.5/7.9
15.5/13.2 23.1/19.8
31.1/26.4
45.1/42
Max. mains fuses
See section
Fuses
Estimated power
loss [W], Best case/
typical
1)
12/14
15/18
21/26
48/60
80/102
97/120
Weight enclosure
IP20 [kg]
2.
2.0
2.0
2.1
3.4
4.5
7.9
7.9
9.5
Efficiency [%], Best
case/Typical 1
97.0/96.5 97.3/96.8 98.0/97.6 97.6/97.0 97.1/96.3 97.9/97.4
1) At rated load conditions
Quick Guide
VLT HVAC Basic Drive FC 101 Quick Guide
MG.18.A1.02 - VLT
®
is a registered Danfoss trademark
25
1
1