1.3.6 Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire
hazard, all branch circuits in an installation, switch gear,
machines etc., must be short-circuit and overcurrent
protected according to national/international regulations.
Short circuit protection:
Danfoss recommends using the fuses mentioned in the
following tables to protect service personnel or other
equipment in case of an internal failure in the unit or short-
circuit on DC-link. The frequency converter provides full
short circuit protection in case of a short-circuit on the
motor.
Overcurrent protection:
Provide overload protection to avoid overheating of the
cables in the installation. Overcurrent protection must
always be carried out according to national regulations.
Fuses must be designed for protection in a circuit capable of
supplying a maximum of 100,000A
rms
(symmetrical), 480V
maximum.
Non UL compliance:
If UL/cUL is not to be complied with, Danfoss recommends
using the fuses mentioned in the below table, which will
ensure compliance with IEC61800-5-1:
In case of malfunction, not following the fuse recommen-
dation may result in damage to the frequency converter.
UL
Non
UL
Bussmann Bussmann Bussmann Bussmann Max.
Fuse
Power
kW
Type RK5 Type RK1 Type J
Type T
Type
gG
3 x 200-240V
0.25
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
0.37
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
0.75
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
1.5
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
2.2
FRS-R-15
KTN-R15
JKS-15
JJN-15
16
3.7
FRS-R-25
KTN-R25
JKS-25
JJN-25
25
5.5
FRS-R-50
KTN-R50
JKS-50
JJN-50
50
7.5
FRS-R-50
KTN-R50
JKS-50
JJN-50
50
11
FRS-R-80
KTN-R80
JKS-80
JJN-80
65
3 x 380-480V
0.37
FRS-R-10
KTS-R10
JKS-10
JJS-10
10
0.75
FRS-R-10
KTS-R10
JKS-10
JJS-10
10
1.5
FRS-R-10
KTS-R10
JKS-10
JJS-10
10
2.2
FRS-R-15
KTS-R15
JKS-15
JJS-15
15
3
FRS-R-15
KTS-R15
JKS-15
JJS-15
15
4
FRS-R-15
KTS-R15
JKS-15
JJS-15
15
5.5
FRS-R-25
KTS-R25
JKS-25
JJS-25
25
7.5
FRS-R-25
KTS-R25
JKS-25
JJS-25
25
11
FRS-R-50
KTS-R50
JKS-50
JJS-50
50
15
FRS-R-50
KTS-R50
JKS-50
JJS-50
50
18.5
FRS-R-80
KTS-R80
JKS-80
JJS-80
65
22
FRS-R-80
KTS-R80
JKS-80
JJS-80
65
30
FRS-R-80
KTS-R80
JKS-R80
JJS-R80
80
37
FRS-R-100
KTS-R100
JKS-R100
JJS-R100
100
45
FRS-R-125
KTS-R125
JKS-R125
JJS-R125
125
55
FRS-R-150
KTS-R150
JKS-R150
JJS-R150
150
75
FRS-R-200
KTS-R200
JKS-R200
JJS-R200
200
90
FRS-R-250
KTS-R250
JKS-R250
JJS-R250
250