Parameter Overview

*[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-33 FC Port Parity
*[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
0.001 - 0.500s, * 0.010
8-36 Max Response Delay
0.100 - 10.000s, *5.000
8-37 Max Inter-char delay
0.025 - 0.025s, * 0.025

8-5* Digital/Bus

8-50 Coasting Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-51 Quick Stop Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-52 DC Brake Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-53 Start Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-54 Reversing Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-55 Set-up Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-56 Preset Reference Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR

8-7* Bacnet

8-70 BACnet Device Instance
0 - 0x400000UL
* 1

8-72 MS/TP Maxmaster
0 - 127, * 127
8-73 MS/TP Max Info Frames
1 - 65534, * 1
8-74 "I am" Service
*[0] Send at power-up
[1] Continuously
8-75 Intialisation Password

8-8* FC Port Diagnostics

8-80 Bus Message Count
0 - 65536, * 0
8-81 Bus Error Count
0 - 65536, * 0
8-82 Slave Message Rcvd
0 - 65536, * 0
8-83 Slave Error Count
0 - 65536, * 0
8-84 Slave Message Sent
0 - 65536, * 0
8-85 Slave Timeout Errors
0 - 65536, * 0
8-88 Reset FC port Diagnostics
*[0] Do not reset
[1] Reset counter

8-9* Bus Feedback
8-94 Bus feedback 1

-32768 - 32767, * 0

13-** Smart Logic
13-0* SLC Settings

13-00 SL Controller Mode
*[0] Off
[1] On
13-01 Start Event
[0] False
[1] True
[2] Running
[3] In range
[4] On reference
[7] Out of current range
[8] Below I

low

[9] Above I

high

[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
[33] Digital input 18
[34] Digital input 19

[35] Digital input 27
[36] Digital input 29
*[39] Start command
[40] Drive stopped
[41] Reset trip
[42] Auto reset trip
[43] Key Ok
[44] Key Reset
[47] Key Up
[48] Key Down
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[83] Broken belt
13-02 Stop Event
See par. 13-02, *[40] Drive stopped
13-03 Reset SLC
*[0] Do not reset
[1] Reset SLC

13-1* Comparators

13-10 Comparator Operand
*[0] Disabled
[1] Reference
[2] Feedback
[3] Motor speed
[4] Motor current
[6] Motor power
[7] Motor voltage
[8] DC-link voltage
[12] Analog in 53
[13] Analog in 54
[20] Alarm number
[30] Counter A
[31] Counter B
13-11 Comparator Operator
[0] Less Than
*[1] Approx. Equal
[2] GreaterThan
13-12 Comparator Value
-9999.0 - 9999.0, * 0.0

13-2* Timers

13-20 SL Controller Timer
0.00 - 3600.00, * 0.00

13-4* Logic Rules

13-40 Logic Rule Boolean 1
See par. 13-01, *[0] False
13-41 Logic Rule Operator 1
*[0] Disabled
[1] AND
[2] OR
[3] AND NOT
[4] OR NOT
[5] NOT AND
[6] NOT OR
[7] NOT AND NOT
[8] NOT OR NOT

13-42 Logic Rule Boolean 2
See par. 13-01, *[0] False
13-43 Logic Rule Operator 2
See par. 13-41, *[0] Disabled
13-44 Logic Rule Boolean 3
See par. 13-01, *[0] False

13-5* States

13-51 SL Controller Event
See par. 13-01, *[0] False
13-52 SL Controller Action
*[0] Disabled
[1] No action
[2] Select set-up 1
[3] Select set-up 2
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[25] Qstop
[26] DC Brake
[27] Coast
[28] Freeze output
[29] Start timer 0
[30] Start timer 1
[31] Start timer 2
[32] Set digital out A low
[33] Set digital out B low
[34] Set digital out C low
[35] Set digital out D low
[38] Set digital out A high
[39] Set digital out B high
[40] Set digital out C high
[41] Set digital out D high
[60] Reset Counter A
[61] Reset Counter B
[70] Start timer 3
[71] Start timer 4
[72] Start timer 5
[73] Start timer 6
[74] Start timer 7
[100] Reset Alarm

14-** Special Functions
14-0* Inverter Switching

14-01 Switching Frequency
[0] Ran3
[1] Ran5
[2] 2.0 kHz
[3] 3.0 kHz
[4] 4.0 kHz

Quick Guide

VLT HVAC Basic Drive FC 101 Quick Guide

MG.18.A1.02 - VLT

®

 is a registered Danfoss trademark

21

1

1

Summary of Contents for VLT HVAC Basic Drive FC 10

Page 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT HVAC Basic Drive FC 101...

Page 2: ...t Electrical Installation 7 1 3 8 Control Terminals 9 1 3 9 Electrical Overview 10 1 4 Programming 11 1 4 1 Programming with the Local Control Panel LCP 11 1 4 2 The FC 101 Start up Wizard for Open Lo...

Page 3: ...nt in the protective conductor Where a residual current device RCD is used for extra protection only an RCD of Type B time delayed shall be used on the supply side of this product See also Danfoss App...

Page 4: ...ether with domestic waste It must be separately collected with electrical and electronic waste according to local and currently valid legislation 1 3 Installation 1 3 1 Before Starting Repair Work 1 D...

Page 5: ...0 24 8 690 27 2 521 20 5 313 12 3 270 10 6 335 13 2 8 5 H8 IP20 90kW 120Hp 660 26 800 31 5 631 24 8 375 14 8 330 13 335 13 2 8 5 Table 1 1 Mechanical Dimensions 1 3 4 Electrical Installation in Genera...

Page 6: ...e please see instruction MI 02 QX YY Also see EMC Correct Installation in the Design Guide MG 18 CX YY 1 Mount the earth wires to earth terminal 2 Connect motor to terminals U V and W 3 Mount mains su...

Page 7: ...function not following the fuse recommen dation may result in damage to the frequency converter UL Non UL Bussmann Bussmann Bussmann Bussmann Max Fuse Power kW Type RK5 Type RK1 Type J Type T Type gG...

Page 8: ...since this ruins the screening effect at high frequencies Use cable clamps instead It is important to ensure good electrical contact from the installation plate through the installation screws to the...

Page 9: ...PLC etc Panel Mains supply Min 200mm between control cable mains cable and between mains motor cable PLC Protective earth Reinforced protective earth 130BB761 10 Illustration 1 2 EMC correct Electric...

Page 10: ...par 5 00 PNP is default value and digital input 29 mode is set in par 5 03 PNP is default value Control terminals The illustration below shows all control terminals of the frequency converter Applying...

Page 11: ...OV PNP Bus ter Bus ter RS 485 Interface RS 485 N PS 485 69 P RS 485 68 Com RS 485 61 PNP Source NPN Sink ON Terminated OFF Unterminated ON 1 2 240Vac 2A Not present on all power sizes Do not connect...

Page 12: ...s to Quick Menus Main Menu For access to all parameters Navigation Keys Back For moving to the previous step or layer in the navigation structure Arrows For navigating between parameter groups paramet...

Page 13: ...R2 R1 0 10V Reference Start 10V A IN A IN COM 130BB674 10 45 The wizard will initially be shown after power up until any parameter has been changed The wizard can always be accessed again through the...

Page 14: ...ion of Relay 2 0 No function Selected Function of Relay 1 0 No function Set Max Reference 0050 Hz Set Min Reference 0 Hz AMA running OK OK B a c k Status Main Menu Quick Menu Hand On OK Menu Off Reset...

Page 15: ...ble the drive to catch a spinning motor 6 19 Terminal 53 mode 0 Current 1 Voltage 1 Select if terminal 53 is used for current or voltage input 6 10 Terminal 53 Low Voltage 0 10V 0 07V Enter the voltag...

Page 16: ...a 20 21 22 23 32 33 34 35 36 37 0 03 Regional Settings 0 International 4 13 Motor speed low limit 0016 Hz 4 13 Motor speed high limit 0050 Hz 1 130BB631 10 1 20 Motor Power 1 10 kW 1 23 Motor frequenc...

Page 17: ...for current or voltage input 6 10 Terminal 53 Low Voltage 0 10V 0 07V Enter the voltage that corresponds to the low reference value 6 11 Terminal 53 High Voltage 0 10V 10V Enter the voltage that corre...

Page 18: ...drive to catch a spinning motor Changes Made Changes Made lists all parameters changed since factory setting Only the changed parameters in current edit setup are listed in changes made If the parame...

Page 19: ...LCP 2 All from LCP 3 Size indep from LCP 0 51 Set up Copy 0 No copy 1 Copy from setup 1 2 Copy from setup 2 9 Copy from Factory setup 0 6 Password 0 60 Main Menu Password 0 999 0 1 Load and Motor 1 0...

Page 20: ...0 0 4 63 Bypass Speed To Hz 0 0 400 0 0 0 4 64 Semi Auto Bypass Set up 0 Off 1 Enable 5 Digital In Out 5 0 Digital I O mode 5 00 Digital Input Mode 0 PNP 1 NPN 5 03 Digital Input 29 Mode 0 PNP 1 NPN 5...

Page 21: ...nd activ 168 Drive in hand mode 169 Drive in auto mode 193 Sleep Mode 194 Broken Belt Function 196 Fire Mode 198 Bypass Mode 6 73 Terminal 45 Output Min Scale 0 00 200 00 0 00 6 74 Terminal 45 Output...

Page 22: ...input 29 39 Start command 40 Drive stopped 41 Reset trip 42 Auto reset trip 43 Key Ok 44 Key Reset 47 Key Up 48 Key Down 50 Comparator 4 51 Comparator 5 60 Logic rule 4 83 Broken belt 13 02 Stop Event...

Page 23: ...verter Serial Number 15 53 Power Card Serial Number 16 Data Readouts 16 0 General Status 16 00 Control Word 0 65535 0 16 01 Reference Unit 4999 000 4999 000 0 000 16 02 Reference 200 0 200 0 0 0 16 03...

Page 24: ...hase on supply side or too high voltage imbalance Check supply voltage See parameter 14 12 7 11 DC over volt X X Internediate circuit voltage exceeds limit 8 10 DC under volt X X Intermediate circuit...

Page 25: ...mit 60 44 External Interlock X External interlock has been activated To resume normal operation apply 24V DC to the terminal programmed for external interlock and reset the frequency converter via ser...

Page 26: ...rmittent 3x200 240V A 1 7 2 4 4 6 7 5 10 6 16 7 24 2 30 8 46 2 Max input current RELAY 2 130BB633 10 40 C ambient temperature Continuous 3x200 240V A 1 1 1 6 2 8 5 6 8 8 7 2 14 1 12 21 18 28 3 24 41 3...

Page 27: ...0V A 1 2 2 3 3 7 5 3 6 9 9 0 12 1 15 4 23 1 Max input current RELAY 2 130BB633 10 40 C ambient temperature Continuous 3x380 440V A 1 2 2 1 3 5 4 7 6 3 8 3 11 2 15 1 22 1 Intermittent 3x380 440V A 1 3...

Page 28: ...46 Max mains fuses See section Fuses Estimated power loss W Best case typical 1 Weight enclosure IP20 kg 7 9 9 5 9 5 24 5 24 5 24 5 36 36 51 Efficiency Best case Typical 1 1 At rated load conditions 1...

Page 29: ...degree 2 The unit is suitable for use on a circuit capable of delivering not more than 100 000 RMS symmetrical Amperes 240 480 V maximum Motor Output U V W Output voltage 0 100 of supply voltage Outpu...

Page 30: ...ial Communication Terminal number 68 P TX RX 69 N TX RX Terminal number 61 Common for terminals 68 and 69 Control Card 24V DC Output Terminal number 12 Max load enclosure frame H1 H8 80mA Relay Output...

Page 31: ...erating 1000m Maximum altitude above sea level with derating 3000m Derating for high altitude see section on special conditions Safety standards EN IEC 61800 5 1 UL 508C EMC standards Emission EN 6180...

Page 32: ...www danfoss com drives MG18A102 130R0192 MG18A102 Rev 2010 06 02...

Page 33: ......

Reviews: