![background image](http://html1.mh-extra.com/html/danfoss/vlt-automationdrive-fc-301/vlt-automationdrive-fc-301_operating-manual_3414831055.webp)
525–600 V
Recommended maximum fuse
Power
[kW
(hp)]
Bussmann
Type RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
SIBA
Type RK1
Littelfuse
Type RK1
Ferraz
Shawmut
Type RK1
Ferraz
Shawmut
J
0.75–
1.1
(1.0–
1.5)
KTS-R-5
JKS-5
JJS-6
FNQ-R-5
KTK-R-5
LP-CC-5
5017906-005
KLS-R-005
A6K-5-R
HSJ-6
1.5–2.2
(2.0–
3.0)
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
5017906-010
KLS-R-010
A6K-10-R
HSJ-10
3.0
(4.0)
KTS-R15
JKS-15
JJS-15
FNQ-R-15
KTK-R-15
LP-CC-15
5017906-016
KLS-R-015
A6K-15-R
HSJ-15
4.0
(5.0)
KTS-R20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5017906-020
KLS-R-020
A6K-20-R
HSJ-20
5.5
(7.5)
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
5017906-025
KLS-R-025
A6K-25-R
HSJ-25
7.5
(10.0)
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
5017906-030
KLS-R-030
A6K-30-R
HSJ-30
11
(15.0)
KTS-R-35
JKS-35
JJS-35
–
–
–
5014006-040
KLS-R-035
A6K-35-R
HSJ-35
15.0
(20.0)
KTS-R-45
JKS-45
JJS-45
–
–
–
5014006-050
KLS-R-045
A6K-45-R
HSJ-45
18.5
(25.0)
KTS-R-50
JKS-50
JJS-50
–
–
–
5014006-050
KLS-R-050
A6K-50-R
HSJ-50
22.0
(30.0)
KTS-R-60
JKS-60
JJS-60
–
–
–
5014006-063
KLS-R-060
A6K-60-R
HSJ-60
30.0
(40.0)
KTS-R-80
JKS-80
JJS-80
–
–
–
5014006-080
KLS-R-075
A6K-80-R
HSJ-80
37.0
(50.0)
KTS-R-100
JKS-100
JJS-100
–
–
–
5014006-100
KLS-R-100
A6K-100-R
HSJ-100
45.0
(60.0)
KTS-R-125
JKS-125
JJS-125
–
–
–
2028220-125
KLS-R-125
A6K-125-R
HSJ-125
55.0
(75.0)
KTS-R-150
JKS-150
JJS-150
–
–
–
2028220-150
KLS-R-150
A6K-150-R
HSJ-150
75.0
(100.0)
KTS-R-175
JKS-175
JJS-175
–
–
–
2028220-200
KLS-R-175
A6K-175-R
HSJ-175
Table 8.21 525–600 V, Enclosure Sizes A, B, and C
Specifications
Operating Guide
MG33AT02
Danfoss A/S © 05/2018 All rights reserved.
53
8
8