525–600 V
Enclosure Power [kW (hp)]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit
breaker
Moeller
Maximum trip level
[A]
A2
0-75-4.0 (1.0–5.0)
gG-10
gG-25
PKZM0-25
25
A3
5.5 (7.5)
gG-10
gG-32
PKZM0-25
25
7.5 (10.0)
gG-16
A5
5.5 (7.5)
gG-10
gG-32
PKZM0-25
25
7.5 (10.0)
gG-16
B1
11.0 (15.0)
gG-25
gG-80
PKZM4-63
63
15.0 (20.0)
gG-32
18.5 (25.0)
gG-40
B2
22.0 (30.0)
gG-50
gG-100
NZMB1-A100
100
30.0 (40.0)
gG-63
B3
11.0 (15.0)
gG-25
gG-63
PKZM4-50
50
15.0 (20.0)
gG-32
B4
18.5 (25.0)
gG-40
gG-125
NZMB1-A100
100
22.0 (30.0)
gG-50
30.0 (40.0)
gG-63
C1
37.0 (50.0)
gG-63
gG-160
NZMB2-A200
160
45.0 (60.0)
gG-100
55.0 (60.0)
aR-160
aR-250
C2
75.0 (100.0)
aR-200
aR-250
NZMB2-A250
250
C3
37.0 (50.0)
gG-63
gG-150
NZMB2-A200
150
45.0 (60.0)
gG-100
gG-150
NZMB2-A200
C4
55.0 (75.0)
aR-160
aR-250
NZMB2-A250
250
75.0 (100.0)
aR-200
Table 8.15 525–600 V, Enclosure Sizes A, B, and C
525–690 V
Enclosure Power [kW (hp)]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit
breaker
Moeller
Maximum trip level
[A]
A3
1.1 (1.5)
1.5 (2.0)
2.2 (3.0)
3.0 (4.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10.0)
gG-6
gG-6
gG-6
gG-10
gG-10
gG-16
gG-16
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
PKZM0-16
16
B2/B4
11.0 (15.0)
15.0 (20.0)
18.5 (25.0)
22.0 (30.0)
gG-25
gG-32
gG-32
gG-40
gG-63
–
–
B4/C2
30.0 (40.0)
gG-63
gG-80
–
–
C2/C3
37.0 (50.0)
45.0 (60.0)
gG-63
gG-80
gG-100
gG-125
–
–
C2
55.0 (75.0)
75.0 (100.0)
gG-100
gG-125
gG-160
–
–
Table 8.16 525–690 V, Enclosure Sizes A, B, and C
Specifications
VLT
®
AutomationDrive FC 301/302
50
Danfoss A/S © 05/2018 All rights reserved.
MG33AT02
8