Type designation
P37K
P45K
P55K
P75K
High/normal load
1)
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output [kW/(hp)]
37 (50)
45 (60)
45 (60)
55 (75)
55 (75) 75 (100) 75 (100) 90 (125)
Enclosure protection rating IP20
C3
C3
C3
C4
C4
Enclosure protection rating IP21, IP55, IP66
C1
C1
C1
C2
C2
Output current
Continuous (525–550 V) [A]
54
65
65
87
87
105
105
137
Intermittent (525–550 V) [A]
81
72
98
96
131
116
158
151
Continuous (551–600 V) [A]
52
62
62
83
83
100
100
131
Intermittent (551–600 V) [A]
78
68
93
91
125
110
150
144
Continuous kVA (550 V) [kVA]
51.4
61.9
61.9
82.9
82.9
100.0
100.0
130.5
Continuous kVA (575 V) [kVA]
51.8
61.7
61.7
82.7
82.7
99.6
99.6
130.5
Maximum input current
Continuous at 550 V [A]
49
59
59
78.9
78.9
95.3
95.3
124.3
Intermittent at 550 V [A]
74
65
89
87
118
105
143
137
Continuous at 575 V [A]
47
56
56
75
75
91
91
119
Intermittent at 575 V [A]
70
62
85
83
113
100
137
131
Additional specifications
IP20 maximum cable cross-section
5)
for mains and
motor [mm
2
] ([AWG])
50 (1)
150 (300 MCM)
IP20 maximum cable cross-section
5)
for brake and load
sharing [mm
2
] ([AWG])
50 (1)
95 (4/0)
IP21, IP55, IP66 maximum cable cross-section
5)
for
mains and motor [mm
2
] ([AWG])
50 (1)
150 (300 MCM)
IP21, IP55, IP66 maximum cable cross-section
5)
for
brake and load sharing [mm
2
] ([AWG])
50 (1)
95 (4/0)
Maximum cable cross-section
2),5)
for mains disconnect
[mm
2
] ([AWG])
50, 35, 35
(1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350 MCM, 300
MCM, 4/0)
Estimated power loss at rated maximum load [W]
3)
740
900
900
1100
1100
1500
1500
1800
Efficiency
4)
0.98
0.98
0.98
0.98
Table 8.9 Mains Supply 525–600 V P37K–P75K (FC 302 only), P37K–P75K
For fuse ratings, see chapter 8.7 Fuses and Circuit Breakers.
1) High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2) The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
3) Applies to dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to
drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/
4) Efficiency measured at nominal current. For energy efficiency class, see chapter 8.4 Ambient Conditions. For part load losses, see
drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
5) Cable cross-section is regarded for copper cables.
Specifications
Operating Guide