![Danfoss VLT AutomationDrive FC 301 Operating Manual Download Page 15](http://html1.mh-extra.com/html/danfoss/vlt-automationdrive-fc-301/vlt-automationdrive-fc-301_operating-manual_3414831015.webp)
e30bf228.11
L1
L2
L3
PE
PE
u
v
w
2
1
3
5
16
17
18
14
12
8
7
10
9
4
11
13
4
6
15
90
1
PLC.
10
Mains cable (unshielded).
2
Minimum 16 mm
2
(6 AWG) equalizing cable.
11
Output contactor.
3
Control cables.
12
Cable insulation stripped.
4
Minimum 200 mm (7.9 in) between control cables, motor
cables, and mains cables.
13
Common ground busbar. Follow local and national
requirements for cabinet grounding.
5
Mains supply.
14
Brake resistor.
6
Bare (unpainted) surface.
15
Metal box.
7
Star washers.
16
Connection to motor.
8
Brake cable (shielded).
17
Motor.
9
Motor cable (shielded).
18
EMC cable gland.
Illustration 4.3 Example of Proper EMC Installation
Electrical Installation
Operating Guide
MG33AT02
Danfoss A/S © 05/2018 All rights reserved.
13
4
4