380–500 V
Enclosure Power [kW (hp)]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit
breaker Moeller
Maximum trip level
[A]
A1
0.37–1.5 (0.5–2.0)
gG-10
gG-25
PKZM0-16
16
A2
0.37–3.0 (0.5–4.0)
gG-10
gG-25
PKZM0-25
25
4.0 (5.0)
gG-16
A3
5.5–7.5 (7.5–10.0)
gG-16
gG-32
PKZM0-25
25
A4
0.37–3.0 (0.5–4.0)
gG-10
gG-32
PKZM0-25
25
4.0 (5.0)
gG-16
A5
0.37–3.0 (0.5–4.0)
gG-10
gG-32
PKZM0-25
25
4.0–7.5 (5.0–10.0)
gG-16
B1
11–15 (15.0–20.0)
gG-40
gG-80
PKZM4-63
63
B2
18.5 (25.0)
gG-50
gG-100
NZMB1-A100
100
22.0 (30.0)
gG-63
B3
11–15 (15.0–20.0)
gG-40
gG-63
PKZM4-50
50
B4
18.5 (25.0)
gG-50
gG-125
NZMB1-A100
100
22.0 (30.0)
gG-63
30.0 (40.0)
gG-80
C1
30.0 (40.0)
gG-80
gG-160
NZMB2-A200
160
37.0 (50.0)
gG-100
45.0 (60.0)
gG-160
C2
55.0 (75.0)
aR-200
aR-250
NZMB2-A250
250
75.0 (100.0)
aR-250
C3
37.0 (50.0)
gG-100
gG-150
NZMB2-A200
150
45.0 (60.0)
gG-160
gG-160
C4
55.0 (75.0)
aR-200
aR-250
NZMB2-A250
250
75.0 (100.0)
aR-250
Table 8.14 380–500 V, Enclosure Sizes A, B, and C
Specifications
Operating Guide
MG33AT02
Danfoss A/S © 05/2018 All rights reserved.
49
8
8