FC 302
P400
P500
P560
High/Normal load*
HO
NO
HO
NO
HO
NO
Typical shaft output at 550 V [kW]
315
400
400
450
450
500
Typical shaft output at 575 V [HP]
400
500
500
600
600
650
Typical shaft output at 690 V [kW]
400
500
500
560
560
630
Enclosure IP21
E1
E1
E1
Enclosure IP54
E1
E1
E1
Enclosure IP00
E2
E2
E2
Output current
Continuous (at 550 V) [A]
429
523
523
596
596
630
Intermittent (60 s overload) (at 550 V) [A]
644
575
785
656
894
693
Continuous (at 575/690 V) [A]
410
500
500
570
570
630
Intermittent (60 s overload) (at 575/690 V)
[A]
615
550
750
627
855
693
Continuous KVA (at 550 V) [KVA]
409
498
498
568
568
600
Continuous KVA (at 575 V) [KVA]
408
498
498
568
568
627
Continuous KVA (at 690 V) [KVA]
490
598
598
681
681
753
Maximum input current
Continuous (at 550 V) [A]
413
504
504
574
574
607
Continuous (at 575 V) [A]
395
482
482
549
549
607
Continuous (at 690 V) [A]
395
482
482
549
549
607
Max. cable size, line power, motor and load
share [mm
2
(AWG)
1)
]
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
Max. cable size, brake [mm
2
(AWG)
1)
]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Max. external electrical fuses [A]
2)
700
900
900
Estimated power loss at 600 V [W]
3) 4)
4795
6010
6493
7395
7383
8209
Estimated power loss at 690 V [W]
3) 4)
4970
6239
6707
7653
7633
8495
Weight, enclosure IP21, IP54 [kg]
263
272
313
Weight, enclosure IP00 [kg]
221
236
277
Efficiency
4)
0.98
Output frequency
0–500 Hz
Heatsink overtemp. trip
230 °F [110
°
C]
Power card ambient trip
185 °F [85
°
C[
* High overload=160% torque during 60 s, Normal overload=110% torque during 60 s.
Table 4.9 Technical Specifications, E-frame 525–690 V Line Power Supply 3x525–690 V AC
1) American Wire Gauge.
2) For fuse ratings, see chapter 7.2.1 Fuses.
3) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the adjustable frequency drive.
If the switching frequency is raised from nominal, the power losses rise significantly. LCP and typical control card power consumptions are
included. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B
each add only 4 W.
4) Measured using 16.5 ft. [5 m] shielded motor cables at rated load and rated frequency.
Selection
Design Guide
72
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG34S222
4
4