FC 302
P450
P500
P560
P630
P710
P800
High/Normal load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 400 V [kW]
450
500
500
560
560
630
630
710
710
800
800
1000
Typical shaft output at 460 V [HP]
600
650
650
750
750
900
900
1000
1000
1200
1200
1350
Typical shaft output at 500 V [kW]
530
560
560
630
630
710
710
800
800
1000
1000
1100
Enclosure IP21, IP54 without/with
options cabinet
F1/ F3
F1/ F3
F1/ F3
F1/ F3
F2/ F4
F2/ F4
Output current
Continuous (at 400 V) [A]
800
880
880
990
990
1120
1120
1260
1260
1460
1460
1720
Intermittent (60 s overload)
(at 400 V) [A]
1200
968
1320
1089
1485
1232
1680
1386
1890
1606
2190
1892
Continuous (at 460/500 V) [A]
730
780
780
890
890
1050
1050
1160
1160
1380
1380
1530
Intermittent (60 s overload)
(at 460/500 V) [A]
1095
858
1170
979
1335
1155
1575
1276
1740
1518
2070
1683
Continuous kVA (at 400 V) [kVA]
554
610
610
686
686
776
776
873
873
1012
1012
1192
Continuous kVA (at 460 V) [kVA]
582
621
621
709
709
837
837
924
924
1100
1100
1219
Continuous kVA
(at 500 V) [kVA]
632
675
675
771
771
909
909
1005
1005
1195
1195
1325
Maximum input current
Continuous (at 400 V) [A]
779
857
857
964
964
1090
1090
1227
1227
1422
1422
1675
Continuous (at 460/500 V) [A]
711
759
759
867
867
1022
1022
1129
1129
1344
1344
1490
Max. cable size, motor [mm
2
(AWG)
1)
]
8x150 (8x300 mcm)
12x150 (12x300 mcm)
Max. cable size, line power F1/F2
[mm
2
(AWG)
1)
]
8x240 (8x500 mcm)
Max. cable size, line power F3/F4
[mm
2
(AWG)
1)
]
8x456 (8x900 mcm)
Max. cable size, load sharing [mm
2
(AWG)
1)
]
4x120 (4x250 mcm)
Max. cable size, brake
[mm
2
(AWG)
1)
4x185 (4x350 mcm)
6x185 (6x350 mcm)
Max. external electrical fuses [A]
2)
1600
2000
2500
Estimated power loss
at 400 V [W]
3) 4)
9031
10162
10146
11822 10649 12512 12490 14674 14244 17293 15466 19278
Estimated power loss
at 460 V [W]
3)
4)
8212
8876
8860
10424
9414 11595 11581 13213 13005 16229 14556 16624
F3/F4 max. added losses A1 RFI, CB
or Disconnect, & contactor F3/F4
893
963
951
1054
978
1093
1092
1230
2067
2280
2236
2541
Max. panel options losses
400
Weight, enclosure IP21, IP54 [kg]
1017/1318
1260/1561
Weight, rectifier module [kg]
102
102
102
102
136
136
Weight, inverter module [kg]
102
102
102
136
102
102
Efficiency
4)
0.98
Output frequency
0–590 Hz
Heatsink overtemp. trip
230 °F [110 °C]
Control card ambient trip
185 °F [85 °C]
* High overload=160% torque during 60 s, Normal overload=110% torque during 60 s.
Table 4.3 Technical Specifications, F-frames, 380–500 V Line Power Supply 3x380–500 V AC
1) American Wire Gauge.
2) For fuse ratings, see chapter 7.2.1 Fuses.
3) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the adjustable frequency drive.
Selection
Design Guide
66
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG34S222
4
4