FC 302 [kW]
Drive internal Bussmann PN
Rating
Alternate Siba PN
630
170M8611
1100 A, 1000 V
20 781 32.1000
710
170M8611
1100 A, 1000 V
20 781 32.1000
800
170M8611
1100 A, 1000 V
20 781 32.1000
900
170M8611
1100 A, 1000 V
20 781 32.1000
1000
170M8611
1100 A, 1000 V
20 781 32.1000
1200
170M8611
1100 A, 1000 V
20 781 32.1000
Table 7.38 525–690 V, Frame Size F, Inverter Module DC Link Fuses
1)
170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of
the same size and amperage may be substituted for external use
2)
Any minimum 500 V UL listed fuse with associated current rating may be used to meet UL requirements.
7.2.6 Supplementary Fuses
Supplementary Fuses
Frame size
Bussmann PN
Rating
D
LPJ-21/2SP
2.5 A, 600 V
Table 7.39 D-frame Anti-Condensation Heater Fuse Recommendation
NOTICE!
If a D-frame adjustable frequency drive comes with an anti-condensation heater, the heater must be powered,
controlled, and protected by the installing contractor.
Frame size
Bussmann PN
Rating
E and F
KTK-4
4 A, 600 V
Table 7.40 SMPS Fuse
Size/Type
Bussmann PN
LittelFuse
Rating
P355-P400,
525–690 V
KTK-4
4 A, 600 V
P315-P800,
380–500 V
KLK-15
15 A, 600 V
P500-P1M2,
525–690 V
KLK-15
15 A, 600 V
Table 7.41 Fan Fuses
Electrical Installation
Design Guide
MG34S222
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
213
7
7