9.8 MCB 113 Extended Relay Card
The MCB 113 adds seven digital inputs, two analog
outputs, and four SPDT relays to the standard I/O of the
adjustable frequency drive, providing increased flexibility
and compliance with the German NAMUR NE37
recommendations.
The MCB 113 is a standard C1-option for the Danfoss VLT
®
AutomationDrive and is detected automatically after
mounting.
For information on mounting and installing the option, see
130BA965.10
12
11
10
9
8
7
6
5
4
3
2
1
4
3
2
1
12
11
10
9
8
7
6
5
4
3
2
1
2
1
13 14
+
- + -
+
-
+
- + - + - + - + - + - + -
A03
A03
Ex
t. 24
VDC
DI1
DI2
DI3
DI4
DI5
DI6
DI7
X45/
X48/
X46/
X47/
Rela
y 3
Rela
y 4
Rela
y 5
Rela
y 6
Figure 9.17 Electrical Connections of MCB 113
MCB 113 can be connected to an external 24 V on X58/ in
order to ensure galvanic isolation between the VLT
®
AutomationDrive and the option card. If galvanic isolation
is not needed, the option card can be powered through
internal 24 V from the adjustable frequency drive.
NOTICE!
It is acceptable to combine 24 V signals with high
voltage signals in the relays as long as there is one
unused relay in-between.
To set up MCB 113, use parameter groups
5-1* Digital
Inputs
,
6-7* Analog Output 3
,
6-8* Analog Output 4
,
14-8*
Options
,
5-4* Relays
, and
16-6* Inputs and Outputs
.
NOTICE!
In parameter group
5-4* Relays
, array [2] is relay 3, array
[3] is relay 4, array [4] is relay 5, and array [5] is relay 6.
Options and Accessories
Design Guide
MG34S222
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
261