FC 302
P315
P355
P400
High/Normal load*
HO
NO
HO
NO
HO
NO
Typical shaft output at 400 V [kW]
315
355
355
400
400
450
Typical shaft output at 460 V [HP]
450
500
500
600
550
600
Typical shaft output at 500 V [kW]
355
400
400
500
500
530
Enclosure IP21
E1
E1
E1
Enclosure IP54
E1
E1
E1
Enclosure IP00
E2
E2
E2
Output current
Continuous (at 400 V) [A]
600
658
658
745
695
800
Intermittent (60 s overload)
(at 400 V) [A]
900
724
987
820
1043
880
Continuous (at 460/500 V) [A]
540
590
590
678
678
730
Intermittent (60 s overload)
(at 460/500 V) [A]
810
649
885
746
1017
803
Continuous kVA (at 400 V) [kVA]
416
456
456
516
482
554
Continuous kVA (at 460 V) [kVA]
430
470
470
540
540
582
Continuous kVA (at 500 V) [kVA]
468
511
511
587
587
632
Maximum input current
Continuous (at 400 V) [A]
590
647
647
733
684
787
Continuous (at 460/500 V) [A]
531
580
580
667
667
718
Max. cable size, line power, motor and
load share [mm
2
(AWG)]
1)2)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
Max. cable size, brake [mm
2
(AWG)
1)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Max. external electrical fuses [A]
3)
900
900
900
Estimated power loss at 400 V [W]
4)
5)
6794
7532
7498
8677
7976
9473
Estimated power loss at 460 V [W]
4) 5)
6118
6724
6672
7819
7814
8527
Weight, enclosure IP21, IP54 [kg]
270
272
313
Weight, enclosure IP00 [kg]
234
236
277
Efficiency
5)
0.98
Output frequency
0–590 Hz
Heatsink overtemp. trip
230 °F [110 °C]
Control card ambient trip
185 °F [85 °C]
* High overload=160% torque during 60 s, Normal overload=110% torque during 60 s.
Table 4.2 Technical Specifications, E-frame 380–500 V Line Power Supply 3x380–500 V AC
1) American Wire Gauge.
2) Wiring terminals on N132, N160, and P315 adjustable frequency drives cannot receive cables one size larger.
3) For fuse ratings, see chapter 7.2.1 Fuses.
4) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the adjustable frequency drive.
If the switching frequency is raised from nominal, the power losses rise significantly. LCP and typical control card power consumptions are
included. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B
each add only 4 W.
5) Measured using 16.5 ft. [5 m] shielded motor cables at rated load and rated frequency.
Selection
Design Guide
MG34S222