The relay option does not support FC 302 adjustable
frequency drives manufactured before week 50/2004.
Min. software version: 2.03 (
15-43 Software Version
).
2
130BA709.11
1
LABEL
Rem
ove jumpe
r to a
ctiva
te S
afe S
top
12
13
18
19
27
29
33
32
20
39
42
50
53
54
61
68
CAUTION:
SEE
MANU
AL / R
CD an
d high leak
age
curren
t
VOIR M
ANUAL
/ Fransk t
ekst
WARNING:
Stored
char
ge /
“Fransk
tekst” (4
min.)
LISTED 7
6x1 134
261
IND
USTRI
AL C
ONTR
OL EQ
UIP
MENT
SEE M
ANU
AL FOR PREFUS
E TUPE IN UL
APPLIC
ATIONS
T/C
: CIA
XXXPT5B20
BR1DBF00A
00
P/N : X
XXN11
00 S/N:
012815G432
IN: 3x380
-480V 50/60H
z 14.9A
OUT
: 3x0-Uin 0-
1000H
z 16.0A
11.1 kV
A
CHAS
IS/IP20
Tamb M
ax 45
C/113F
MADE IN DENM
ARK
9Ø
9Ø
Ø6
Figure 9.9 A2, A3, and B3
2
130BA710.11
1
LABEL
Remove jump
er to activate S
afe Stop
13
12
18 19 27
32 38 2
28
42
39
53
50
5
616
9Ø
9Ø
DC- DC+
Figure 9.10 A5, B1-B4, and C1-C4
1)
IMPORTANT!
The label MUST be placed on the LCP
frame as shown in
to meet UL approval.
WARNING
Warning Dual supply. Do not combine 24/48 V systems
with high voltage systems.
To add the MCB 105 option, perform the following steps:
•
The power to the adjustable frequency drive
must be disconnected. For discharge times, see
the instructions supplied with this option
•
The power to the live part connections on relay
terminals must be disconnected. See
•
Remove the LCP, the terminal cover, and the LCP
fixture from the adjustable frequency drive
•
Fit the MCB 105 option in slot B
•
Connect the control cables and fasten the cables
with the enclosed cable strips.
•
Make sure the length of the stripped wire is
correct. See
•
Do not mix the live parts (high voltage) with the
control signals (PELV). See
•
Fit the enlarged LCP fixture and enlarged
terminal cover
•
Replace the LCP.
•
Connect power to the adjustable frequency drive
•
Select the relay functions in
5-40 Function Relay
[6-8],
5-41 On Delay, Relay
[6-8] and
5-42 Off
Delay, Relay
[6-8].
NOTICE!
Array [6] is relay 7, array [7] is relay 8, and array [8] is
relay 9.
Relay 7
NC
NC
NC
Relay 9
Relay 8
1
2
3
12
130BA162.10
7
5
4
6
8
9
10
11
Figure 9.11 Disconnect Relay Terminals
130BA177.10
8-9mm
2mm
Figure 9.12 Proper Length of Stripped Wire
Options and Accessories
Design Guide
MG34S222
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
257
9
9